ClimateMaster 50YDS Series Installation & Operation Manual Download Page 22

Refrigeration Installation

FP2 Sensor Installation
An FP2 sensor with violet wiring is shipped loose with the 
compressor section.  This is the air coil low temperature 
protection sensor.  Install this sensor on the refrigerant line 
between the indoor expansion valve and the air coil using 
thermal compound and the supplied mounting clips.  Ensure 
that the sensor makes good thermal contact with the refrigerant 
line and insulate the sensor.

Air coil low temperature protection will not be active if this 
sensor is installed incorrectly or is not installed.

Add-On Heat Pump Applications
The indoor coil should be located in the supply side of 
the furnace to avoid condensation damage to the furnace 
heat exchanger for add-on heat pump applications. A high 
temperature limit switch should be installed as shown in 
Figure 11b just upstream of the coil to de-energize the 
compressor any time the furnace is energized to avoid 
blowing hot air directly into the coil, elevating refrigerant 
pressures during operation. The heat pump will trip out on 
high pressure lockout without some method of disengaging 
the compressor during furnace operation. Alternatively, some 
thermostats with “dual fuel” mode will automatically de-
energize the compressor when second stage (backup) heat 
is required.

The TXV should be brazed into place as shown in Figure 10, 
keeping the “IN” side toward the compressor section. The 
TXV has an internal check valve and must be installed in the 
proper direction for operation. Always keep the valve body 
cool with a brazing shield and wet rags to prevent damage 
to the TXV. Attach the bulb to the suction line using the 
supplied hose clamp. Be careful not to overtighten the clamp 
and deform the bulb.

NOTICE! The air coil should be thoroughly washed with a 

Ä

 lming agent, (dishwasher detergent like Cascade) to help 

condensate drainage. Apply a 20 to 1 solution of detergent 
and water. Spray both sides of coil, repeat and rinse 
thoroughly with water. 

Evacuation and Charging the Unit
LEAK TESTING -
 The refrigeration line set must be pressurized 
and checked for leaks before evacuating and charging the unit. 
To pressurize the line set, attach refrigerant gauges to the service 
ports and add an inert gas (nitrogen or dry carbon dioxide) until 
pressure reaches 60-90 psig [413-620 kPa]. Never use oxygen or 
acetylene to pressure test. Use a halogen leak tester or a good 
quality bubble solution to detect leaks on all connections made 
in the 

Ä

 eld. Check the service valve ports and stem for leaks. If 

a leak is found, repair it and repeat the above steps. For safety 
reasons do not pressurize system above 150 psig [1034 kPa]. 
System is now ready for evacuation and charging.
Turn service valves full out CCW (see Table 6) and then turn 
back in one-half turn to open service ports. Add the required 
refrigerant so that the total charge calculated for the unit 

and line set is now in the system. Open the service valve 
fully counter clockwise so that the stem will backseat and 
prevent leakage through the schrader port while it is not in 
use. Start unit in the heating mode and measure superheat 
and subcooling values after 5 minutes of run time. See 
tables 14d for superheat and sub-cooling values. Superheat 
is measured using suction temperature and pressure at the 
compressor suction line. Subcooling should be measured 
using the liquid line temperature immediately outside the 
compressor section cabinet and either the liquid line service 
valve pressure or the compressor discharge pressure. Note 
that different values from tables 14d will be obtained due to 
the pressure losses through the condenser heat exchanger. 
Adding refrigerant will increase sub-cooling while superheat 
should remain fairly constant allowing for a slight amount 
of hunting in TXV systems. This increase in subcooling will 
require 5 minutes or so of operation before it should be 
measured. After values are measured, compare to the chart 
and go to “FINAL EVALUATION.”

PARTIAL CHARGE METHOD - Open service valve fully 
counterclockwise and then turn back in one-half turn to 
open service port. Add vaporized (Gas) into the suction side 
of the compressor until the pressure in the system reaches 
approximately 100-120 psig. Never add liquid refrigerant into 
the suction side of a compressor. Start the unit in heating 
and add gas to the suction port at a rate not to exceed 

Ä

 ve pounds [2.27 kg] per minute. Keep adding refrigerant 

until the complete charge has been entered. Superheat is 
measured using suction temperature and pressure at the 
compressor suction line. Subcooling should be measured 
using the liquid line temperature immediately outside the 
compressor section cabinet and either the liquid line service 
valve pressure or the compressor discharge pressure. Note 
that different values from tables 14d will be obtained due to 
the pressure losses through the condenser heat exchanger. 
Adding refrigerant will increase sub-cooling while superheat 
should remain fairly constant allowing for a slight amount 
of hunting in TXV systems. This increase in subcooling will 
require 5 minutes or so of operation before it should be 
measured. After values are measured, compare to the chart 
and go to “FINAL EVALUATION.”

FINAL EVALUATION -In a split system, cooling subcooling 
values can be misleading depending on the location of the 
measurement. Therefore, it is recommended that charging 
be monitored in the heating mode. Charge should be 
evaluated by monitoring the subcooling in the heating mode. 
After initial check of heating sub-cooling, shut off unit and 
allow to sit 3-5 minutes until pressures equalize. Restart unit 
in the cooling mode and check the cooling superheat against 
Tables 14d. If unit runs satisfactorily, charging is complete. If 
unit does not perform to speci

Ä

 cations the cooling TXV (air 

coil side) may need to be readjusted (if possible) until the 
cooling superheat values are met. 

Checking Superheat and Subcooling

R e s i d e n t i a l   S p l i t   U n i t s   -   6 0 H z   P u r o n

®

R e v. :   6   D e c . ,   2 0 1 1

22

Summary of Contents for 50YDS Series

Page 1: ...utdoor Compressor Section Only 29 30 Electrical Line Voltage 31 Electrical Power Wiring 32 Electrical HWG Wiring 32 Electrical Low Voltage Wiring 33 37 Thermostat Wiring 33 37 CXM Controls 38 40 Unit...

Page 2: ...This page was intentionally left blank...

Page 3: ...FNDJLQJ 5HYLVLRQ HYHO HDW FKDQJHU 2SWLRQV 6 6 WHQGHG 5DQJH 3XURQ 8OWUD LJK IILFLHQF 5HVLGHQWLDO 6SOLW 6HULHV 6 3 7 5 6 1 7 8 1 7 2SWLRQ 5HWXUQ LVFKDUJH LOWHU 1 121 121 121 0RWRU 121 XUUHQW 5HYLVLRQ LW...

Page 4: ...rant circuit oil will remain in the compressor To avoid leakage of compressor oil refrigerant lines of the compressor must be sealed after it is removed Safety Warnings cautions and notices appear thr...

Page 5: ...maximum of 3 units high Unit Protection Cover units on the job site with either the original packaging or an equivalent protective covering Cap the open ends of pipes stored on the job site In areas w...

Page 6: ...heat pumps are rated in the AHRI directory with a speci c indoor coil match GT PX and GT PE models are rated with Carrier Bryant FV4 or FE4 series variable speed air handlers as shown in Table 1a Othe...

Page 7: ...may be used as a 1 1 2 ton unit if locked into 1st stage operation only If PSC fan is used unit must be locked into either 1st or 2nd stage An ECM fan is required for two stage operation and for AHRI...

Page 8: ...43 28 27 0 27 28 43 47 35 39 43 32 36 37 28 32 32 24 26 27 750 61 49 39 55 43 33 48 37 27 41 29 20 33 21 17 0 04 27 27 28 24 25 25 21 22 22 18 18 18 15 15 15 950 74 60 48 67 53 40 59 45 33 50 35 25 3...

Page 9: ...room to make water electrical and line set connections Any access panel screws that would be dif cult to remove after the unit is installed should be removed prior to setting the unit Refer to Figure...

Page 10: ...ctions Residential Distributor Models Residential models utilize swivel piping ttings for water connections that are rated for 450 psi 3101 kPa operating pressure The connections have a rubber gasket...

Page 11: ...power and match the ow rate to the unit s requirements The pump speed selection switch is located on the pump s electrical box 50YPS026 and 038 units come standard with one circulator 50YPS049 and 064...

Page 12: ...ld be avoided due to their potential to leak in earth coupled applications A anged tting should be substituted P T plugs should be used so that ow can be measured using the pressure drop of the unit h...

Page 13: ...section for more details Loop static pressure will uctuate with the seasons Pressures will be higher in the winter months than during the cooling season This uctuation is normal and should be conside...

Page 14: ...ol 100 USP food grade Propylene Glycol Ethanol 25 38 29 21 25 25 16 22 20 10 15 14 Must not be denatured with any petroleum based product Fluid Volume gal liters per 100 30 meters Pipe Pipe Size Volum...

Page 15: ...prevent pump short cycling Discharge water from the unit is not contaminated in any manner and can be disposed of in various ways depending on local building codes e g recharge well storm sewer drain...

Page 16: ...are installed with a factory or eld supplied manual or electric shut off valve DAMAGE WILL OCCUR if shut off valve is closed during unit operation A high pressure switch must be installed on the heat...

Page 17: ...hloride nitrate and sulfate compounds All 0 5 ppm Maximum Maximum Allowable at maximum water temperature Chloride Levels 10 C 24 C 38 C Copper Cupronickel 20ppm NR NR 150 ppm NR NR 304 SS 400 ppm 250...

Page 18: ...essor Section Braze the line set to the service valve stubs as shown in Figure 9 Remove the schraeder cores and heat trap the valves to avoid overheating and damage On installations with long line set...

Page 19: ...il can act as an insulator on the wall of the coil tubing hindering proper heat transfer and thus reducing system ef ciency and capacity Another important reason to thoroughly ush the line set is remo...

Page 20: ...nit is operational follow steps F L F First start the existing R 22 system in the cooling mode and close the liquid line valve G Completely pump all existing R 22 refrigerant into the outdoor unit It...

Page 21: ...this case keeping the cylinder upright 14 Once the liquid refrigerant has been completely recovered switch the recovery machine to vapor recovery so that the R 22 vapor can be completely recovered IMP...

Page 22: ...the system Open the service valve fully counter clockwise so that the stem will backseat and prevent leakage through the schrader port while it is not in use Start unit in the heating mode and measure...

Page 23: ...efrigerant line liquid line just outside of the cabinet This location will be adequate for measurement in both modes unless a signi cant temperature drop in the liquid line is anticipated 2 Determine...

Page 24: ...al Split Add on Coil Fossil Fuel Furnace Installation Compressor Section TXV IN toward Compressor Section TXV IN toward Compressor Section Figure 11a Typical Split Air Handler Installation Insulated L...

Page 25: ...dy for charging Figure 12 Evacuation Graph Charging The System There are two methods of charging a refrigerant system One method is the total charge method where the volume of the system is determined...

Page 26: ...the 125 F set point versus the amount of heat that can be generated by the HWG when using the 150 F set point In a typical 50 gallon two element electric water heater the lower element should be turne...

Page 27: ...PLOY AN APPROVED ANTI SCALD VALVE PART NUMBER AVAS4 AT THE HOT WATER STORAGE TANK WITH SUCH VALVE PROPERLY SET TO CONTROL WATER TEMPERATURES DISTRIBUTED TO ALL HOT WATER OUTLETS AT A TEMPERATURE LEVEL...

Page 28: ...piping with no less than 3 8 10mm wall closed cell insulation 3 Open both shut off valves and make sure the tank drain valve is closed Water Tank Re ll 1 Close valve 4 Ensure that the HWG valves valv...

Page 29: ...stall the Add On HWG Kit Locate the HWG as close to the water heater as possible Install the lineset to the desuperheater valves in the outdoor compressor section and the refrigerant line connections...

Page 30: ...G Bypassed Valve Closed HWG Activated Control Board Circulator HWG Water Out HWG Refr Out HWG Refr In High Voltage HWG Water In Figure 16b Remote HWG Module Capacity Line Set Size 1 2 OD 5 8 OD 3 4 OD...

Page 31: ...208V or 230V WARNING To avoid possible injury or death due to electrical shock open the power supply disconnect switch and secure it in an open position during installation CAUTION Use only copper co...

Page 32: ...e Wiring For Use with Outdoor Compressor Section Consult Electrical Table for wire and fuse size All power wiring per local code L2 L1 T2 T1 HWG Module Wiring For Outdoor Compressor Section The HWG mo...

Page 33: ...is packed inside the compressor section control box Low Water Temperature Cutout Selection The CXM control allows the eld selection of low water or water antifreeze solution temperature limit by clip...

Page 34: ...Electrical LowVoltage Wiring L2 L1 T2 T1 Low Voltage Connector Figure 22 GT PE Low Voltage Field Wiring Re s i d e n t ia l Split Units 60Hz Puron R ev 6 De c 2011 34...

Page 35: ...lications to limit water use during rst stage operation For example at 1 5 gpm ton 2 0 l m per kW a model 049 unit requires 6 gpm 23 l m for full load 2nd stage operation but only 4 gpm 15 l m during...

Page 36: ...correct number of heating and cooling stages Y2 Y1 G R C Y2 Y1 G R C TAH Air Handler T Stat ATP32U03 ATP32U04 Y1 Y2 G R C A L Terminal Blocks in Compressor Section Fan Control Board O O O W W W A C01...

Page 37: ...1 W2 W E Typical Air Handler Typical T stat CXM Board Compressor Section O G R C L AL1 Y2 Y1 Y Y2 From Compressor Solenoid Valve Figure 28b Typical Thermostat Wiring Single Stage Units 2 Heat 1 Cool F...

Page 38: ...mp provides eld selection of temperature limit setting for FP1 of 30 F or 10 F 1 F or 12 C refrigerant temperature Not Clipped 30 F 1 C Clipped 10 F 12 C Air coil low temperature limit setting Jumper...

Page 39: ...ctory for one try Therefore the control will go into lockout mode once the FP1 fault has occurred FP1 lockout code 4 Air coil low temperature FP2 The FP2 thermistor temperature must be below the selec...

Page 40: ...hen being activated or being removed O and G are direct pass through signals but are monitored by the micro processor R and C are from the transformer AL1 and AL2 originate from the alarm relay A is p...

Page 41: ...and humidity and or corrosive water or air will adversely affect unit performance reliability and service life Consult 11a for operating limits Cooling Heating Air Limits Min ambient air DB 45 F 7 C 3...

Page 42: ...lag and strong chemical cleaning agents Some antifreeze solutions may require distilled water Flow Controller pump s Verify that the pump s is wired purged of air and in operating condition System con...

Page 43: ...between the entering and leaving water and GPM is the ow rate in U S GPM determined by comparing the pressure drop across the heat exchanger to Table 14 f Check air temperature drop across the air co...

Page 44: ...155 145 155 145 155 473 493 458 478 441 461 7 12 7 12 7 12 10 15 10 15 9 14 13 6 15 6 9 9 11 9 6 2 8 2 16 22 16 22 16 22 Operation Not Recommended Based on 15 methanol antifreeze solution Entering Wa...

Page 45: ...26 115 125 160 180 133 153 125 145 16 21 17 22 18 23 8 13 6 11 5 10 17 5 19 5 11 9 13 9 6 3 8 3 16 22 16 22 16 22 66 76 69 79 72 82 282 302 285 305 289 309 9 15 9 15 9 15 8 13 8 13 9 14 8 10 6 8 4 6 2...

Page 46: ...ons In areas with extremely hard water a HWG is not recommended Filters Filters must be clean to obtain maximum performance Filters should be inspected every month under normal operating conditions an...

Page 47: ...ernal fan relay units with PSC motors only The alarm relay can either be 24VAC as shipped or dry contacts for use with DDC controls by clipping the JW1 jumper Electric heat outputs are 24VDC ground si...

Page 48: ...ontrol board Yes No No No No No Yes No Yes See HP Fault See LP LOC Fault See FP1 Fault See FP2 Fault See Condensate Fault See Over Under Voltage No fault shown Replace CXM See Unit short cycles See On...

Page 49: ...ure out of range Too much cold vent air Bring entering air temp within design parameters X Improper temperature limit setting 30 F vs 10 F 1 C vs 12 C Normal airside applications will require 30 F 1 C...

Page 50: ...re weigh in charge X X Restricted metering device Check superheat and subcooling per chart Replace Low Suction Pressure X Reduced water ow in heating Check pump operation or water valve operation set...

Page 51: ...1 9 9 22 1 3 16 21 9 9 5 2 48 1 7 1 3 16 21 9 9 22 1 3 16 21 9 9 36 6 7 36 6 7 5 1 5 6 7 21 2035 6625 6 7 21 5 1 5 6 7 21 2035 6625 6 7 21 RROLQJ H SDQVLRQ YDOYH PHWHUV LQ WKH FRROLQJ PRGH DQG E SDVVH...

Page 52: ...QWHQDQFH UHSDLU ZLULQJ RU YROWDJH FRQGLWLRQV 3URGXFWV VXEMHFWHG WR DFFLGHQW PLVXVH QHJOLJHQFH DEXVH UH RRG OLJKWQLQJ XQDXWKRUL HG DOWHUDWLRQ PLVDSSOLFDWLRQ FRQWDPLQDWHG RU FRUURVLYH DLU RU OLTXLG VXSS...

Page 53: ...Notes 53 Residential Split Units 60Hz Puron Rev 6 Dec 2 0 1 1...

Page 54: ...e management system governing the manufacture of Manufacturer s products is ISO 9001 2000 certi ed LSB Inc 2009 Date Page Description 6 Dec 11 36 ATP32U03 4 Wiring Figure Added 31 Jan 11 18 Refrigeran...

Reviews: