Multi-Appliance Comfort Control
Controls- Installation / Setup / Commissioning
S
ETTING UP THE
D
UMP
V
ALVE
(W
HERE
F
ITTED
)
Dump valve settings have two parts to the setup.
•
Setting the dumping cycle time
•
Setting the Dump OFF delay time.
S
ETTING THE
D
UMP
OFF
D
ELAY
T
IME
.
Dump OFF Delay Time gives the option for immediate dumping of
the water from the Tank or a one hour delay after the unit has been
turned OFF. Setting the 1 hour delay is preferable if the unit is going
to be used in thermostat (AUTO) mode. To set the 1 hour delay:
1.
Make sure the unit is in MANUAL mode and is set to COOL
FRESH AIR.
2.
Press the
ENTER
button and the
MANUAL/AUTO
buttons
together for 10 seconds. Press the ENTER button first. The
word OPT and some numbers will flash on the screen.
3.
Using the
▼
or
▲
buttons make the top number read 00.
Press
ENTER.
4.
Using the
▼
or
▲
buttons change the number of the second
line to 01. Press
ENTER.
The one hour delay is now set.
S
ETTING THE
D
UMPING
C
YCLE
T
IMES
1.
Make sure the unit is in MANUAL mode and is set to COOL
FRESH AIR.
2.
Press the
ENTER
button and the
MANUAL/AUTO
buttons
together for 10 seconds. Press the ENTER button first. The
word OPT and some numbers will flash on the screen.
3.
Using the
▼
or
▲
buttons make the top number reads 01.
Press
ENTER.
4.
Using the
▼
or
▲
buttons change the number of the second
line to hourly required between dumping the water from the
tank. Press
ENTER
. Dumping Cycles can be 0, 1, 2, 4, 8, 12,
24 hours.
The dumping cycle times have now been set.
Comfort Control - PNE