Multi-Appliance Comfort Control
Controls- Installation / Setup / Commissioning
SETTING UP THE CONTROLS – DUCTED GAS CENTRAL HEATING
S
ETTING
M
INIMUM
F
AN
S
PEED
1.
Using the
MANUAL/AUTO
button set the unit to MANUAL.
2.
Using the
ECONOMY/BOOST
button set the unit to
ECONOMY.
3.
Press the
ENTER
and
ECONOMY/ BOOST
buttons for
approximately 10 seconds pressing the ENTER button first.
4.
The words FAN SPEED and a number under the room
temperature will flash.
5.
Adjust minimum fan speed to 27 or a number suitable that the
heater does not go out on over-temperature.
Press
ENTER
to keep new fan speed.
S
ETTING
M
AXIMUM
F
AN
S
PEED
1.
Using the
MANUAL/AUTO
button set the unit to MANUAL
2.
Using the
ECONOMY/BOOST
button set the unit to BOOST
3.
Press the
ENTER
and
ECONOMY/ BOOST
buttons for
approximately 10 seconds pressing the ENTER button first.
4.
The words FAN SPEED and a number between the 2 bars will
flash.
5.
Adjust maximum fan speed to 35 or a number suitable that the
unit does not go out on over-temperature.
Press ENTER to keep new fan speed.
Setting the fan speeds to a low setting should be completed by an authorised installer / service technician.
Motor warranty may be voided for incorrect settings.
S
ETTING
T
HE
Z
ONE
A
VAILABILITY
The unit default is for all zones to be available. To filter out the zones not being used:
1.
Press the
ENTER
and
CLEAN FILTER/ZONE ABCD
buttons for 10 seconds pressing the ENTER
button first.
2.
Using the
▼
or
▲
buttons select the zone combination required AB, ABC or ABCD.
3.
Press ENTER to keep the combination.
Now only the zone combination selected will be available for use when operating the zone requirements.
Comfort Control - PNE
Page 40