Multi-Appliance Comfort Control
Ducted Evaporative Air Conditioning
P
ROBLEM
S
OLVING
PROBLEM
PROBABLE CAUSE
REMEDY
a
Black – out
a
Wait
b
Tripped Circuit Breaker
b
Reset
c Blown
Fuse
c Replace
Unit fails to start
d Electrical
Fault
d Call
Climate
Technologies
Service Provider
a
Pump Seized
a
Isolate power and then take off
top of pump and try to free it.
Some lubricant may help.
Pump fails to start
b
Pump Burnt Out
b
Call Climate Technologies
Service Provider
a
Float Valve Leaking
a
Check adjustment or replace
seal
Water leaking from
overflow
b
Drain from Celdek Pads
b
Normal Operation
a
Loose Delivery Tube
a
Check and tighten
b
Break in tubing
b
Replace as necessary
Water Droplets in
air stream
c
Pump Delivers Excessive Water to
Pads
c
Adjust the Dialflo to reduce the
flow
a
Inadequate Exhaust
a
Provide more open area to
exhaust stale air
Excessive humidity
b
Outside humidity high
b
Turn pump off.
a Dirty
Filters
a Clean
b
Dry Filters
b
Check water delivery system.
Adjust if necessary.
Inadequate Cooling
c
Dialflo not set correctly
c
Adjust Dialflo so that the pads
have even saturation.
a
Unit located near odor source
a
Remove source
Unpleasant Odor
b
New Celdek filter smell
b
Smell will disappear after a
period of operation.
Rapid formation of
white deposits on
pads
High Mineral Content
Bleed off should be set at
maximum. More regular
maintenance may be required.
THIS TROUBLE SHOOTING GUIDE IS A REFERENCE ONLY.
FOR SERVICE OR WARRANTY REQUIREMENTS PLEASE REFER
TO THE LAST PAGE OF THESE INSTRUCTIONS