Room thermostat MTC
adverse effect on the correct measurement of the room temperature and hen
operation of the thermostat.
By pressing the notch on the bottom of the thermostat, you can open the thermostat. The bottom plate
containing the connector can be mounted on a universal wall box or directly on the wall.
Be ware that the controller should not be mounted near a an
communication network. These antennas may disturb the correct functioning of the controller.
Always keep a few meters distance.
Place the thermostat in a place where you can see the
to reset a heater, the effect must be visible.
4.2 Electrical connection
In all cases the communication between the heater and the
thermostat is based on a two wire, low
the appliance the wire for the thermostat has to be connected
to connection 4 and 5 (see also electrical wiring diagram).
Connect the thermostat wires to the connector
marked with RT
If the right connector is used the thermostat will
become defect.
Cable specification: signal cable, 1x2x0,8 (shielded and twisted)
Maximum length 200m.
If the cable is chosen too thin, the signal will become too poor. If the cable is not shielded and twisted
the signal might become disturbed in an EMC unfriendly environment.
Keep the thermostat cable separated from mains cables. Connect the earth shield of the cable only to
the earth terminal in the heater.
If these guidelines are not followed it may result in malfunction of the installation or worse, it could
damage the thermostat or the electron
4.3 One heater on one controller
Standard nothing needs to be changed in the heating device. In case the
thermostat does not work, check that the micro
plate in the room heater are set as shown on the right: number
and the other numbers down. The switch S3 should be set to 1. In case
several devices are connected to 1 thermostat, refer to the relevant chapter
in this manual.
This thermostat is only suitable for connection to heating devices specifically intended for this
purpose. Never connect, for example, 24V or another voltage of another system to the thermostat.
This can damage the thermostat.After making the changes insid
plug the power to the heater for the changes to become effective.
4.4 Several units on 1 thermostat
The room thermostat can control up to 8 room heaters. Connecting
them is simple, but it should be done properly.
Pay attention to the following:
•
Each unit must be given its own number (to be set with the
micro-switch S2 in the unit).
•
One unit must have the S2 number 1 set on ON (this unit
provides for the communication) and S3 to 1, al the other
heaters should have S3 set to 0.
•
Between the separate units, the numbers 4 must be
connected with the numbers 4 and the number 5 with 5. They must not be connected in a
cross-wise manner.
The functionality of the thermostat does not change by connecting a number of room heaters.
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
ON
S2
adverse effect on the correct measurement of the room temperature and hen
By pressing the notch on the bottom of the thermostat, you can open the thermostat. The bottom plate
containing the connector can be mounted on a universal wall box or directly on the wall.
ontroller should not be mounted near a antennas from any internal
communication network. These antennas may disturb the correct functioning of the controller.
Always keep a few meters distance.
Place the thermostat in a place where you can see the heater(s). When the thermostat is used
to reset a heater, the effect must be visible.
In all cases the communication between the heater and the
thermostat is based on a two wire, low-voltage connection. In
the thermostat has to be connected
to connection 4 and 5 (see also electrical wiring diagram).
Connect the thermostat wires to the connector
If the right connector is used the thermostat will
ble, 1x2x0,8 (shielded and twisted)
If the cable is chosen too thin, the signal will become too poor. If the cable is not shielded and twisted
the signal might become disturbed in an EMC unfriendly environment.
ble separated from mains cables. Connect the earth shield of the cable only to
If these guidelines are not followed it may result in malfunction of the installation or worse, it could
damage the thermostat or the electronics in the heater.
One heater on one controller
Standard nothing needs to be changed in the heating device. In case the
thermostat does not work, check that the micro-switches S2 on the print
plate in the room heater are set as shown on the right: number 1 up (ON)
and the other numbers down. The switch S3 should be set to 1. In case
several devices are connected to 1 thermostat, refer to the relevant chapter
This thermostat is only suitable for connection to heating devices specifically intended for this
purpose. Never connect, for example, 24V or another voltage of another system to the thermostat.
This can damage the thermostat.After making the changes inside the heater always unplug and re
plug the power to the heater for the changes to become effective.
Several units on 1 thermostat
The room thermostat can control up to 8 room heaters. Connecting
them is simple, but it should be done properly.
Each unit must be given its own number (to be set with the
switch S2 in the unit).
One unit must have the S2 number 1 set on ON (this unit
provides for the communication) and S3 to 1, al the other
heaters should have S3 set to 0.
Between the separate units, the numbers 4 must be
connected with the numbers 4 and the number 5 with 5. They must not be connected in a
The functionality of the thermostat does not change by connecting a number of room heaters.
4/12
1 2 3 4 5 6 7 8
ON
1
0
S3
S2
5 6 7 8
5 6 7 8
5 6 7 8
Heater 1
Heater 2
Heater 3
0
1
S3
0
1
0
1
adverse effect on the correct measurement of the room temperature and hence on the proper
By pressing the notch on the bottom of the thermostat, you can open the thermostat. The bottom plate
containing the connector can be mounted on a universal wall box or directly on the wall.
ennas from any internal
communication network. These antennas may disturb the correct functioning of the controller.
heater(s). When the thermostat is used
If the cable is chosen too thin, the signal will become too poor. If the cable is not shielded and twisted
ble separated from mains cables. Connect the earth shield of the cable only to
If these guidelines are not followed it may result in malfunction of the installation or worse, it could
Standard nothing needs to be changed in the heating device. In case the
switches S2 on the print
1 up (ON)
and the other numbers down. The switch S3 should be set to 1. In case
several devices are connected to 1 thermostat, refer to the relevant chapter
This thermostat is only suitable for connection to heating devices specifically intended for this
purpose. Never connect, for example, 24V or another voltage of another system to the thermostat.
e the heater always unplug and re
connected with the numbers 4 and the number 5 with 5. They must not be connected in a
The functionality of the thermostat does not change by connecting a number of room heaters.