![ClimAir Multi Therm-C Operating Instructions Manual Download Page 10](http://html.mh-extra.com/html/climair/multi-therm-c/multi-therm-c_operating-instructions-manual_2624565010.webp)
Room thermostat MTC
10/12
Heater 1 XR NG ADJ.
Error A1 (1)
IGNIT ERROR
Reset heater
Heater Error
20,5 ºC
Heater 1 N.C.
Heater 1 XR NG 10kW
STANDBY_0
Tcy Ttop 23
Tx1 22 Tx2 22
Heater 1 XR NG 10kW
STANDBY_0
Ion 0 Ac 0 SF 0
Mi3480 Ig4740 Ma6000
The thermostat can not communicate with the heaters.
Check if the dipswitches are set up right.
Error from the heater
When one or more heater(s) has an error message, it appears
on the display of the thermostat.
By pressing the Info button, you can obtain more information about the error message. With the + and
– buttons, you can select different heaters if connected.
When, for this error message, resetting the room heater is an
option, this also appears in the display. You can reset the heater
by pressing OK.
NOTE: If a room heater frequently goes on failure, do not
continue to reset; this can damage it. Let a recognised installer
examine the room heater.
17 Obtaining extra information from the connected heaters
When the info button is pressed for 5 seconds a special information menu is showed. By pressing the
+ or – button the status of all the connected heaters can be checked. By pressing the Info button
again more information about the selected heater will appear. The information will be shown in the
English language.
To exit the information menu press the M button.
When no heater is found the display will show Heater N.C. not connected
Screen 1
Shows the heater type
Screen 2
line 1: shows the discription of the connected heater
line 2: shows the status of the heater line 3 and 4: shows the temperatures from the internal sensors.
Ycy = flue temperature if the sensor is fitted (optional)
Ttop: temperature of the air where the heater is located.
Tx1 and Tx2: Temperatures from the sensor mounted on the
heatexchanger
screen 3
line 1: shows the discription of the connected heater
line 2: shows the status of the heater
line 3 and 4:
Ion = ionisation level 0 -90
Ac = actual speed or the burnerfan
Sf = actual modulation level of the system fan 0-255
Mi = minimum speed of the burnerfan
Ig = ignition speed of the burnerfan
Ma = maximum speed of the burnerfan
Screen 4
Line 1: Shows the connected heater
Line 2: status
Line 2: Nr of days that the heater is on electric power.
Line 4: Nr of burning hours.
Screen 5
Line 1: Shows the connected heater
Line 2: Nr of success ignitions.
Line 3: Nr of failed ignitions.
Line 4: Nr of flame failures.
Heater 1 HA NG 50KW
Heater 1 HA NG 50KW
BURN_0
Appl.act.days : 15
Burn.act.hours
: 25
Heater 1 HA NG 50KW
Ignit.OK : 20
Ignit.failed : 2
Flame failures: 1