Cleveland 24CGA6.2S Operation Installation Maintenance Manual Download Page 34

34 

d)

As the unit generates steam, the water level fluctuates and a clicking sound is heard as the
solenoid opens and closes the fill valve. The level in the cylinder rises and falls between the
upper and lower fill limit as the fill valve operates.

e)

Check for steam leaks around the door.

f)

KEYPAD CONTROL

When  the  timer  counts  down  to  zero  (00:00),  the  burners  turn  OFF,  the  condenser  flow
stops*  (*models  24CGA6.2S  &  24CGA10.2  only),  and  the  buzzer  sounds  continuously.
Press the START/STOP key to silence the buzzer.

DIAL TIMER CONTROL

When  the  timer  counts  down  to  zero,  the  burners  turn  OFF,  the  condenser  flow  stops*
(*models 24CGA6.2S & 24CGA10.2 only), and the buzzer sounds for 3 seconds.

g) After about 30 seconds steam stops entering the cooking compartment.

12). Turn the steamer OFF by turning the ON/OFF  lever/switch counterclockwise  to  the OFF (top) 

position.  The  red  indicator  light  turns  OFF  immediately,  and  the  automatic  blowdown  cycle 
starts. DO NOT turn OFF the power at the main power switch until blowdown is complete. The 
cycle takes about 3 minutes. 

13). When blowdown is complete, turn the steamer OFF at the main power switch. 

14). Install  the  side  panels  and  secure  them  in  place  with  the  screws.    After  completing  the 

Startup and Blowdown Inspection procedure, and the Operating Test procedure; the steamer 
is ready for service. Refer to the OPERATORs section for complete operating instructions. 

CHAPTER 8 

PREVENTATIVE MAINTENANCE AND 
TROUBLESHOOTING 

A. MAINTENANCE

Maintenance  on  the  steamer  must  be  performed  on  a  regular  basis  to  keep  the  unit  running  properly.  By 
following the maintenance instructions in this chapter and referring to installation section, problems with the 
steamer  will  be  kept  to  a  minimum.  As  with  any  preventative  maintenance  schedule,  the  frequency  of 
steamer  maintenance  may  need  to  be  increased,  depending  on  equipment  usage  and  water  quality.  If 
problems do occur, refer to the Troubleshooting Guide in this chapter. For more information on products and 
services, contact your sales representative.  

1.

Maintenance Records

Make  a  file  solely  for  maintenance  records.  Keep  a  written  record  of  daily,  weekly,  monthly,  and  yearly 
maintenance.  These  records  will  protect  warranty  coverage,  help  personnel  to  know  when  to  perform 
various maintenance procedures, and assist service personnel. 

2.

Daily Maintenance

a.

Blowdown Steam Generator

Blowdown  each  steam  generator  according  to  the  steam  generator  blowdown  instructions  in
Chapter 5.

b.

Clean the Steamer

Clean interior and exterior of the steamer according to the shutdown instructions in Chapter 5.

Summary of Contents for 24CGA6.2S

Page 1: ...eration Installation Maintenance Manual This manual is updated as new information and models are released Visit our website for the latest manual MODELS 24CGA6 2S 24CGA6 2SES 24CGA10 2 24CGA10 2ES For...

Page 2: ...nformer aux mesures de s curit normalis es de l industrie y compris mais sans s y limiter les r glementations de l OSHA les proc dures de d branchement verrouillage tiquetage relatives tous les servic...

Page 3: ...juste modificaci n servicio o mantenimiento puede ocasionar da os a la propiedad lesiones o muerte Lea detenidamente las instrucciones de instalacion y de operaci n antes de instalar poner a funcionar...

Page 4: ...de presi n Keep clear of pressure relief discharge Restez l cart de la soupape de suret Permanezca alejado de la descarga de presi n Do not lean on or place objects on the equipment Ne vous penchez p...

Page 5: ...ER ___________________________________ 14 A OPERATING AND COOKING PROCEDURE TIMED MODE ______________________ 14 B OPERATING AND COOKING PROCEDURE MANUAL MODE ____________________ 15 CHAPTER 5 SHUTDOW...

Page 6: ...y must encompass all of these factors This Operational Safety section outlines the minimum safety policies that should be considered when using one or more Gemini steamers It is assumed that any opera...

Page 7: ...ice representatives to service the steamer if any improper operation of the burner system is suspected 6 Operating personnel must be able to recognize problems and report them so that corrective actio...

Page 8: ...nto the cooking compartment C POWER ON AUTOMATIC FILL When each steamer compartment is turned ON it automatically fills its steam generator with water Use this procedure at the beginning of a shift to...

Page 9: ...ently E INSPECTING THE COOKING COMPARTMENT At the back of the cooking compartment a drain screen covers the drain Refer to Figure 2 2 The screen prevents large food particles from entering and blockin...

Page 10: ...esign of the STEAMSAVER Technology SST The energy saver models provide steam in a similar manner to our high capacity models except that the flow of steam is regulated by cycling the burners off once...

Page 11: ...perature 1 SURECOOK Indicator Light This light is lit whenever the cooking compartment has not yet reached cooking temperature Note when in the timed mode the timer will not count down as long as this...

Page 12: ...manual and timed The TIMED MANUAL rocker switch selects the operating mode Pressing the MANUAL end of the switch selects the manual operating mode Pressing the TIMED end of the switch selects the time...

Page 13: ...e manual mode and lights the red indicator built into the manual end of the switch See also the Note at the bottom of this page Pressing the TIMED end of the switch selects the timed mode 6 Power on I...

Page 14: ...mer starts and stops the steaming operation 1 Inspect and clean the drain and cooking compartment as required Refer to INSPECT THE COOKING COMPARTMENT IN Chapter 2 Part E 2 If necessary preheat the co...

Page 15: ...n during this shift perform the Power OFF and Shut Down and Cleaning Procedures found in Chapter 5 A OPERATING AND COOKING PROCEDURE MANUAL MODE Manual mode allows the operator to personally control t...

Page 16: ...ill be used again in a few minutes shut the door to maintain the cooking compartment temperature If another use is not planned for more than half an hour leave the cooking compartment door slightly op...

Page 17: ...turned fully to the OFF position to properly START the automatic blowdown of the steamer B SHUT DOWN AND CLEANING This procedure should be performed at the end of each day or shift 1 Refer to Power O...

Page 18: ...el No STEAMSAVER 24CGA10 2ES is 24 inches wide a Convection steamer Gas powered and an Atmospheric steam generator with a capacity for 10 cooking pans this model has the extra suffix 2 to differentiat...

Page 19: ...ces should the Steam Vent See Figure 1 2 be removed capped or attached to piping of any kind This fitting is an auxiliary safety intended to prevent any pressure from building up in the generator in t...

Page 20: ...a Location and Clearance Requirements of the Steamer For safe and efficient operation observe the following criteria when selecting an operating location for the Gemini steamer 1 The unit should be i...

Page 21: ...as flue opening on top of the steamer and meet the following requirements 1 The Gemini gas steamer must be vented in accordance with all local state and national codes for venting gas fired appliances...

Page 22: ...d and Drug Administration FDA and WITH THE applicable Federal State or Local plumbing codes 2 Do not install the steamer directly over a drain Steam rising out of the drain will adversely affect opera...

Page 23: ...ain will adversely affect operation cooling air ventilation and may damage electrical components 3 The total length of pipe and number of bend fittings required to reach the open drain determines the...

Page 24: ...in the absence of local codes with the National Fuel Gas Code ANSI Z223 1 latest edition or the Natural Gas Installation Code CAN CGA B149 1 or the Propane Installation Code CAN CGA B149 2 as applica...

Page 25: ...cified on the steamers rating plate and be made in accordance with the following requirements a The steamer must be grounded and have the electrical power lines installed in accordance with local code...

Page 26: ...ements Scale Forming Factors Total Dissolved Solids less than 60 parts per million Silica less than 13 parts per million Alkalinity less than 20 parts per million Corrosion Causing Factors Free Chlori...

Page 27: ...should be of at least the next largest size of pipe to the connection provided at the steamer b The steamer has IPS fittings for the water connections to the generator and to the condenser These fitt...

Page 28: ...rmed next leave the right side panel off otherwise replace the side panel and secure it to the unit C STARTUP AND CHECKOUT The Startup and Checkout procedure prepares a recently installed or repaired...

Page 29: ...Main Manual gas valve to the open position 2 The controls should be set as follows The main power switch should be in the OFF position The steamer s ON OFF levers switches should be set to the OFF pos...

Page 30: ...rocedure Gas Gemini There are a few operating differences between steamers with the dial timer controls and steamers with the keypad controls The differences in cooking operation of the two types of t...

Page 31: ...ck for plumbing leaks Look at the one inch vent gap between the steamer drainpipe and the floor drain A steady stream of water should be draining from the steamer NOTE The ON OFF lever must be turned...

Page 32: ...lower probe the heating components turn ON and begin to heat the water to steam For mechanical timer models only the SURECOOK light comes ON After a few minutes steam begins to enter the compartment f...

Page 33: ...produce steam is shorter because the water in the steam generator and the cooking compartment were preheated during step 5 The timer automatically starts the step 7 functions after counting down to z...

Page 34: ...h the screws After completing the Startup and Blowdown Inspection procedure and the Operating Test procedure the steamer is ready for service Refer to the OPERATORs section for complete operating inst...

Page 35: ...61741 THESE INSTRUCTIONS ARE FOR USE WITH DISSOLVE DESCALER SOLUTION Cleveland Range Part Nos 106174 or 1061741 ONLY Health Hazard Data Effects of Overexposure This product may cause a burning sensati...

Page 36: ...g with water add 1 gallon of DISSOLVE descaler solution into each descaling port While adding liquid to the unit through the descaler inlets pour it in slowly to avoid overflow 9 After the automatic f...

Page 37: ...er cap from the bottom of the strainer Refer to Figure 3 1 which shows the various strainers supplied with the different steamers 3 On some models the strainers are built into the steamer and are acce...

Page 38: ...cycle on and off as necessary to maintain temperature until the cooking operation is complete The condenser spray is activated to cool the condensate water to the drain automatically through the use...

Page 39: ...switch not engaged or has failed Close door completely If problem persists see note 1 Water line strainer and or external filter system is clogged Clean water supply strainer and or filter system Hi...

Page 40: ...n external power switch and close water supply valve s See note 1 Food takes too long to cook To verify the steamers proper operation see note 6 Pans too close to the bottom of cabinet Put pans in rac...

Page 41: ...TROUBLESHOOTING NOTES 1 If problem is inside the steamer call an authorized service representative Cleveland Range will not pay for warranty repairs by unauthorized repair centers 2 Proper installati...

Page 42: ...ck eggshell and peel The result will be a perfectly hard boiled egg 7 Whenever opening door especially when water or steam is leaking around gasket heed the warning below 8 Replacement descale caps an...

Page 43: ...itchencare com To learn how Welbilt Foodservice and its leading brands can equip you visit our global web site at www welbilt com then discover the regional or local resources available to you Every n...

Reviews: