Section 5 — Commissioning
Hawk 1000
5-10
Part No. 750-366
Figure 5-17.
In the event of a bad remote signal, an alarm message will appear on the screen and the control will revert to
Local/Auto mode.
The <Adjust Gains> button accesses the system PID tuning. Default values are: P=5, I=5, D=0.
Figure 5-18. Adjust Gains
<Adjust Setpoint> allows adjustment of Setpoint 1 and Setpoint 2 (if dual setpoint is configured).
Figure 5-19. Adjust Setpoint
<View Actuator> shows setpoint and feedback signals for all configured actuators.