Section 3 — Hardware Checkout
Hawk 1000
3-4
Part No. 750-366
3.1.4 Burner Control Modbus Address and Baud Rate - CB780E
The CB780E Modbus node address should be set to 05 and the baud rate to 9600. Settings are made using
the 780E keypad display.
Press the left three buttons of the keypad display module for one second, then release.
DISPLAY Setup will appear.
Press the two ENTER buttons at the same time.
Press down arrow until MB ADDRESS is displayed.
Press ENTER buttons at the same time.
Press down arrow twice.
Set Modbus address to 05 by using up and down arrow keys.
Press ENTER buttons at the same time.