Section 5 — Commissioning
Hawk 1000
5-6
Part No. 750-366
Figure 5-9. Adjust actuator
When purge position is set, press <Store Purge>. When prompted with “Store Current Values?”, press <Store
Purge> again to confirm or <Cancel> to re-adjust.
Figure 5-10. Store Purge
Note: If a VFD is present, the VFD purge value is automatically set at 100%.
5.2.2 Store Lightoff
When the purge position has been set, the <Store Lightoff> button will be available on the Combustion Setup
screen. After positioning the actuators in the lightoff position press <Store Lightoff>. A confirmation prompt
will appear as when storing the purge position. When both purge and lightoff have been set, the <Curve
Setup> button will be available.
All values except VFD must be less than 25% to store lightoff.