Section 2 — System Components
Hawk 1000
2-6
Part No. 750-366
2.5 Sensor Inputs
The following table shows the sensors available as standard and as options for steam systems (ST) and for
hot water (HW) systems:
All systems use RTDs with a transmitter to produce 4-20mA output for temperature detection.
2.5.1 Steam Systems:
Steam Pressure
is the primary sensor input to the HAWK 1000 Controller in a Steam System. It transmits a
4-20mA process variable signal to the Controller that is used to control Firing Rate and the Operating Limit
Control.
Stack Flue Gas Temperature
is used for High Stack Temperature alarms and shutdown. It is also used in the
boiler efficiency calculation.
Water Temperature
(mandatory on steam boilers) measures boiler-shell water temperature and is used for
thermal shock protection and hot standby control on steam boilers. The standard location for the thermowell is
a 1/2” NPT coupling at the right-hand side center-line of the boiler shell. If this location is not available, an
unused feedwater connection may be used.
Water Level
sensor is OPTIONAL on steam boilers, but must be a CB Level Master.
2.5.2 Hot Water systems:
Supply Temperature
is the primary sensor input to the HAWK 1000 Controller in a Hot Water system. It
transmits a 4-20mA process variable signal to the Controller that is used to control Firing Rate and the
Operating Limit Control.
Outdoor Temperature
is used in Hot Water Systems with the Outdoor Temperature Reset Option.
Return Temperature
is used in Hot Water Systems with the Return Temperature option and is monitor only.
NOTE:
The
Outdoor Temperature
and
Return Temperature
sensors use the same input. One or the other can
be used with the Hawk 1000, but not both.
Sensor
System
Standard
Optional
Steam Pressure
ST
Yes
Stack Temperature
ST & HW
Yes
Water Temperature
ST
Yes
Water Level
ST
Yes
Supply Temperature
HW
Yes
Outdoor Temperature
HW
Yes
Return Temperature
HW
Yes
Summary of Contents for Hawk 1000
Page 1: ...750 366 07 2013 Hawk 1000 Boiler Control Operation Manual...
Page 4: ......
Page 6: ......
Page 30: ...Section 3 Hardware Checkout Hawk 1000 3 12 Part No 750 366...
Page 54: ...Section 4 System Configuration Hawk 1000 4 24 Part No 750 366...
Page 78: ...Section 6 Diagnostics and Troubleshooting Hawk 1000 6 6 Part No 750 366...
Page 82: ...Section 7 Parts Hawk 1000 7 4 Part No 750 366...