BOILER BOOK CFC-E
DIMENSIONS AND RATINGS
10
Table 1. U.S. Standard Dimensions Model CFC-E Boiler
ITEM
DIMENSIONS (inches)
500
750
1000
1500
2000
A
Overall Height
78.0
78.0
78.0
79.9
79.9
B
Overall Width
34.9
34.9
34.9
35.8
35.8
C
Overall Depth
49.4
49.4
49.4
56
56
D
Width Less Casing
32.1
32.1
32.1
33.0
33.0
E
Gas Connection to Floor
70.3
70.3
70.3
73.9
73.9
F
Side of Casing to Gas Connection
3.7
3.7
3.7
7.1
7.1
G
Side of Casing to Air Inlet
10.8
10.8
10.8
10.8
10.8
H
Top of Casing to Air Inlet
7.7
7.7
7.7
7.1
7.1
J
Floor to Condensate Drain
6.3
6.3
6.3
6.3
6.3
K
Floor to Bottom of Casing
11.0
11.0
11.0
11.0
11.0
L
Side of Base to Flue Outlet (Centered)
7.4
7.4
7.4
8.5
8.5
M
Side of Base to Flue Outlet (Offset)
6.4
6.4
6.4
7.5
7.5
N
Rear of Base to Flue Outlet
6.5
6.5
6.5
7.5
7.5
P
Casing Depth
36.3
36.3
36.3
42.4
42.4
Q
Casing Height
67.0
67.0
67.0
68.9
68.9
R
Floor to Lower Return Connection
16.8
16.8
16.8
16.8
16.8
S
Floor to Upper Return Connection
31.8
31.8
31.8
31.8
31.8
T
Floor to Supply Connection
59.5
59.5
59.5
59.5
59.5
U
Floor to Air vent Connection
66.3
66.3
66.3
66.3
66.3
V
Air Vent Line Projection From Rear of Casing
3.2
3.2
3.2
3.3
3.3
CONNECTIONS
W
Water Low Temp. Return, Class150 RF Flange
2-1/2"
2-1/2"
2-1/2"
4"
4"
X
Water High Temp. Return, Class150 RF Flange
2-1/2"
2-1/2"
2-1/2"
4"
4"
Y
Water Outlet, Class150 RF Flange
2-1/2"
2-1/2"
2-1/2"
4"
4"
Z
Air Vent, NPT
1-1/2"
1-1/2"
1-1/2"
1-1/2"
1-1/2"
AA
Vessel Drain, NPT
1-1/2"
1-1/2"
1-1/2"
1-1/2"
1-1/2"
BB
Flue Gas Outlet
(Standard) - Nominal
6"
6"
8"
8"
8"
(Option) - Nominal
8"
8"
6"
10"
10"
CC
Combustion Air - Nominal
6"
6"
6"
8"
8"
DD
Gas, NPT
1"
1"
1"
1-1/2"
1-1/2"
EE
Condensate Drain, NPT
1"
1"
1"
1"
1"
FF
Electrical Opening, Left or Right
1.6"
1.6"
1.6"
1.6"
1.6"
GG
Safety Relief Valve Vessel Connection, NPT
1-1/4"
1-1/4"
1-1/4"
1-1/4"
1-1/4"
HH
Safety Relief Valve
30 psig Inlet x Outlet, NPT
1" x 1-1/4"
1" x 1-1/4"
1" x 1-1/4"
1" x 1-1/4"
1-1/4" x 1-1/2"
50 psig Inlet x Outlet, NPT
3/4" x 1"
3/4" x 1"
3/4" x 1"
3/4" x 1"
1" x 1-1/4"
60 psig Inlet x Outlet, NPT
3/4" x 1"
3/4" x 1"
3/4" x 1"
3/4" x 1"
1" x 1-1/4"
75 psig Inlet x Outlet, NPT
3/4" x 1"
3/4" x 1"
3/4" x 1"
3/4" x 1"
3/4" x 1"
80 psig Inlet x Outlet, NPT
3/4" x 1"
3/4" x 1"
3/4" x 1"
3/4" x 1"
3/4" x 1"
100 psig Inlet x Outlet, NPT
3/4" x 1"
3/4" x 1"
3/4" x 1"
3/4" x 1"
3/4" x 1"
125 psig Inlet x Outlet, NPT
3/4" x 1"
3/4" x 1"
3/4" x 1"
3/4" x 1"
3/4" x 1"
JJ
Flue Coupling, NPT
3/4"
3/4"
3/4"
3/4"
3/4"
KK
Water Outlet Coupling, NPT
1-1/4"
1-1/4"
1-1/4"
1-1/4"
1-1/4"
FORK POCKETS (inches)
LL
Pocket Height
3.9
3.9
3.9
3.9
3.9
MM
Pocket Width
11.8
11.8
11.8
11.8
11.8
NN
Overall Pocket Width
27.6
27.6
27.6
27.6
27.6
WEIGHTS
Dry Weight (lb)
1298
1298
1396
1861
2041
Shipping Weight (lb)
1413
1413
1511
1986
2166
Operating Weight (lb)
2065
2065
2113
2778
2858
Water Volume (gallon)
92
92
86
110
98
CLEARANCES
Top
14"
Notes:
•
Boiler rear must be accessible for servicing.
•
Side clearance to wall or between boilers.
•
Side clearance typical each side.
Side
3"
Rear
20"
Front
36"
Summary of Contents for CFC-E 1000
Page 1: ...CFC E ClearFire Condensing Boiler Boiler Book 02 2018...
Page 52: ...BOILER BOOK CFC E EXAMPLE SYSTEM SCHEMATICS 52 Figure 38 Primary Secondary Single Boiler...
Page 53: ...BOILER BOOK CFC E EXAMPLE SYSTEM SCHEMATICS 53 Figure 39 Primary Secondary Two Boilers...
Page 54: ...BOILER BOOK CFC E EXAMPLE SYSTEM SCHEMATICS 54 Figure 40 Primary Secondary Three Boilers...
Page 55: ...BOILER BOOK CFC E EXAMPLE SYSTEM SCHEMATICS 55 Figure 41 Primary Variable Flow Single Boiler...
Page 56: ...BOILER BOOK CFC E EXAMPLE SYSTEM SCHEMATICS 56 Figure 42 Primary Variable Flow Two Boilers...
Page 57: ...BOILER BOOK CFC E EXAMPLE SYSTEM SCHEMATICS 57 Figure 43 Primary Variable Flow Three Boilers...
Page 60: ...BOILER BOOK CFC E EXAMPLE SYSTEM SCHEMATICS 60...
Page 61: ...BOILER BOOK CFC E e mail info cleaverbrooks com Web Address http www cleaverbrooks com...