BOILER BOOK CFC-E
ENGINEERING DATA
24
b)
Independent from the hydraulics of the heating system, constant water circulation through each boiler is
required while the boiler is operating (requires a dedicated boiler pump if in a primary/secondary loop
arrangement). Refer to table below for minimum boiler circulation rates.
5)
Minimum over-pressure at the boiler:
For outlet temperatures up to the maximum of 185 deg F (85 deg C), a minimum operating pressure of 30 psig
(2.1 bar) is required.
6)
pH level should be maintained between 8.3 and 10.5
7)
It is recommended to maintain continuous circulation in glycol systems. Where this is impractical (e.g. multiple
boiler systems), a periodic pump exercise routine should be implemented to ensure proper mixture of glycol and to
avoid degradation that naturally occurs with glycol mixtures. This can be as simple as opening a boiler isolation
valve once a day or turning on a boiler circulating pump.
Table 12. Glycol Minimum Flow Recommendations for ClearFire Model CFC-E Boiler
(Minimum required boiler circulation rate (gpm) at maximum firing rate.)
Notes/Limitations:
1.
Maximum firing rate determined by ClearFire CFC-E Glycol Firing Rate Limitation chart (below). Maximum high fire
blower speed set according to chart.
2.
Glycol concentration of 25%-50%. Minimum required system operating pressure is 30 psig.
3.
Maximum system operating temperature of 180 ˚F. Maximum
∆
T of 40˚.
4.
Circulation rates correlate with boiler output based on 92% nominal efficiency.
5.
Standard altitude (<1000' ASL). Contact Cleaver-Brooks for high altitude applications.
6.
Pumps should be sized based on system design
∆
T and minimum required flow rates.
7.
At minimum firing rate, the minimum circulation rate should correspond to the boiler's turndown.
System
∆
T (˚F)
Model-Size
∆
T = 10˚
∆
T = 20˚
∆
T = 30˚
∆
T = 40˚
CFC-E 500
95
47
32
24
CFC-E 750
142
71
47
36
CFC-E 1000
190
95
63
47
CFC-E 1500
285
142
95
71
CFC-E 2000
380
190
127
95
Summary of Contents for CFC-E 1000
Page 1: ...CFC E ClearFire Condensing Boiler Boiler Book 02 2018...
Page 52: ...BOILER BOOK CFC E EXAMPLE SYSTEM SCHEMATICS 52 Figure 38 Primary Secondary Single Boiler...
Page 53: ...BOILER BOOK CFC E EXAMPLE SYSTEM SCHEMATICS 53 Figure 39 Primary Secondary Two Boilers...
Page 54: ...BOILER BOOK CFC E EXAMPLE SYSTEM SCHEMATICS 54 Figure 40 Primary Secondary Three Boilers...
Page 55: ...BOILER BOOK CFC E EXAMPLE SYSTEM SCHEMATICS 55 Figure 41 Primary Variable Flow Single Boiler...
Page 56: ...BOILER BOOK CFC E EXAMPLE SYSTEM SCHEMATICS 56 Figure 42 Primary Variable Flow Two Boilers...
Page 57: ...BOILER BOOK CFC E EXAMPLE SYSTEM SCHEMATICS 57 Figure 43 Primary Variable Flow Three Boilers...
Page 60: ...BOILER BOOK CFC E EXAMPLE SYSTEM SCHEMATICS 60...
Page 61: ...BOILER BOOK CFC E e mail info cleaverbrooks com Web Address http www cleaverbrooks com...