28
Figure 24: Flame Adjustment
RESETTING THE OIL PRIMARY CONTROL
(1) Refer to Figure 25 to locate the oil primary control reset button.
(2) Do not attempt to reset the burner if there is excess oil in the combustion chamber, vapor
has accumulated in the unit, or when the boiler is hot.
Oil flooded combustion chamber:
Turn off power to the boiler and disconnect the burner
cord. Open the clean out door and wipe out the accumulated oil before continuing.
Vapor filled combustion chamber:
Allow the unit to cool for 30 minutes and all vapors to
dissipate before resetting the oil primary control.
(3) When the combustion chamber has cooled, and there is no vapor or excess oil in the
combustion chamber, push the reset button for 3 seconds and release.
(4) If the burner does not restart contact the Clean Energy Heating Systems service
department.
WARNING:
Explosion and Fire Hazard. Failure to follow these instructions could
result in heavy smoke emission, puff back, fire and smoke hazards.
STARTING AND ADJUSTING THE BURNER
COMPRESSED
AIR REGULATOR
CE70036
COMBUSTION AIR
INTAKE