Clary Corporation SN1000 Owners Operating & Maintenance Manual Download Page 11

THE CONTINUOUS POWER COMPANY

SUMMARY OF INDICATORS AND CONTROLS

INPUT POWER

 

-

 

This is system input AC power

protection and interruption for both hot and neutral
lines.  This is a circuit breaker that if tripped, unit
operation will continue on battery reserve.  This
circuit breaker is rated at 20A.

SYSTEM ON/OFF

 

-

 

This is system input enable

switch.  This switch is used to power down the
system.  This switch must be in the 

ON

 position in

order to AC or DC start the UPS.

LOAD

 - Four green L.E.D.s and one red

OVERLOAD L.E.D. that illuminate to update status
of the amount of load the INVERTER is powering at
the UPS system output.  Each green L.E.D.
represents approximately 25% of full load.  As more
load is added to the UPS, the L.E.D.s will
sequentially turn 

"ON"

 until the red L.E.D. comes

"ON"

.  This indicates an OVERLOAD situation and

the system will discontinue operation shortly.

BATTERY

 - Four green L.E.D.s and one green

LOW BATTERY L.E.D. that illuminate to update
status of the battery energy available during a power
outage.  Each green L.E.D. represents
approximately 20% of battery reserve power
available. As battery discharge continues, the
L.E.D.s will sequentially turn 

"OFF"

 until the last

L.E.D. starts to flash.  This indicates a LOW
BATTERY situation and the system will discontinue
operation shortly.  Once utility power is returned to
the system, this bar graph will show an approximate
battery state as it reaches full charge.

AC IN

 - A green L.E.D. that is illuminated when both

the 

INPUT POWER

 Circuit Breaker and the

SYSTEM ON/OFF 

switch are closed and there is

utility power present at the input of the system.

BATTERY ON

 

- A red L.E.D. that is illuminated

when the AC input is interrupted to the power
electronics either externally or internally from the
microprocessor due to an out-of-range situation.
The output load is then supported entirely by battery
energy through INVERTER operation.

INV

 - 

A green L.E.D. that illuminates when the

INVERTER generator is operating and available to
deliver power to the system output.

COLD START

 

-

 

This is a momentary, two position

push button keyswitch.  If no AC utility voltage is
available, it may still be a requirement to initialize
some equipment.  When this switch is pressed in for
at least two seconds, the system will start up on
battery power.  The 

SYSTEM

 

ON/OFF

 Switch must

be in the 

ON

 position for this function to operate.

The green L.E.D. above this switch will light only
while the switch is held in.

LOAD ON/OFF

 

- This is a momentary, two-

position push button keyswitch.  When the system
initially powers up for the first time no INVERTER
generator power will be present at the output load
receptacles at the rear panel.  Once this switch is
pressed in for at least two seconds, output power
will then be enabled to the rear panel outlets.  If the
system should be powered down for any reason
other than with the 

SYSTEM

 

ON/OFF

 Switch, the

output state of these outlets will be remembered by
the internal microprocessor and the UPS will start up
with the output in the state it was last left.  The
output neon lamp, in the center of the panel, will light
when the output has been enabled.

BYPASS

 - A red L.E.D. above the 

AC OUTPUT

Switch will light to indicate when the system output
is operating in the filtered, emergency BYPASS
mode.  This is an unprotected power source that will
not support the load in the event of a power failure.

SILENCE

 - This is a momentary, two position push

button keyswitch.  During a system 

FAULT

 or power

failure, an audible alarm will be present.  If a 

FAULT

condition occurs, the red L.E.D. above this switch
will light.  Once this switch is pressed in for at least
two seconds, the audible alarm will be silenced.  The
L.E.D. above the switch will remain unchanged.

TEST -

 This is a momentary, two position push

button keyswitch.  Battery condition is vital to the
UPS performance, particularly during a power
outage.  During normal operation and if the Battery
Bar Graph shows the battery at a full charge, this
function switch may be used.  By pressing this
switch in for at least two seconds, a battery
acceptance diagnostic will be run by the internal
microprocessor.  If it has been discovered that the
battery is excessively fatigued, the red L.E.D. above
this switch will light advising the user to replace the
internal battery or DC supply.  The system will run
this test on its own approximately every 24 hours.

INSERT INTO DOC. 510-12580-Page –11-

Summary of Contents for SN1000

Page 1: ...of Clary Corporation is proprietary confidential and not to be disclosed disseminated or used except for the purpose provided by CLARY CORPORATION P N 510 12580 A RD 12 29 03 Manufactured by T H E C...

Page 2: ...LE PAGE TABLE OF CONTENTS 1 INTRODUCTION 3 TECHNICAL DESCRIPTION 4 PACKAGING 6 PHYSICAL DESCRIPTION 7 SUMMARY OF INDICATORS AND CONTROLS 11 INSTALLATION 12 OPERATION 13 SIGNALS AND INTERFACING 14 SPEC...

Page 3: ...nance of the UPS and batteries Be aware of the following symbols and their meaning as they appear throughout the manual This equipment generates and uses radio frequency energy and if not installed an...

Page 4: ...owing exactly what patterns the supply utility power maintains and by knowing exactly the condition and life expectancy of the battery reserve Reference the block diagram for a simplified explanation...

Page 5: ...NE EMERGENCY CUTOFF SWITCH VOLTAGE WINDOW DETECTOR COMMON MODE CHOKE RECTIFIER CHARGER POWER FACTOR CORRECTOR DC RAILS MICROPROCESSOR CONTROLLER AC INVERTER GENERATOR LOAD STANDBY BATTERY COMMON MODE...

Page 6: ...it report this to your carrier These units are encapsulated in a protective wrap that comes apart once the product is removed from the shipping carton Save all packing material for future use Take ext...

Page 7: ...nhanced to ensure you have a full understanding of the operation of this system Visual indicators used on the front panel are long lasting very efficient light emitting diodes LED When operating the p...

Page 8: ...rating indicator 11 Bypass indicator 4 Battery Level Charge discharge indicators 12 Alarm Silence switch 5 Load Level Output capacity indicators 13 Fault indicator 6 Cold Start DC start switch 14 Batt...

Page 9: ...IGNAL Open collector signal contacts 17 INPUT Dual pole circuit breaker 21 RS232 Computer communications signals 18 DC INPUT Auxiliary battery connector 22 IDENTIFICATION LABEL 19 SYSTEM OUTPUT 120VAC...

Page 10: ...l Rear Panel Callouts 16 INPUT Terminal Block 3 position 20 Signal Open collector signal contacts 17 INPUT BREAKER Dual pole circuit breaker 21 RS232 Computer communications signals 18 DC input Auxili...

Page 11: ...tility voltage is available it may still be a requirement to initialize some equipment When this switch is pressed in for at least two seconds the system will start up on battery power The SYSTEM ON O...

Page 12: ...o be stored it is recommended to refresh the internal battery at least once every 90 days To do this plug the system in position the power On Off switch to ON press and hold at least two seconds the L...

Page 13: ...nates An intermittent audible alarm will sound The SILENCE Switch may be operated at this time it must be held in for at least 2 seconds to quiet the alarm As battery discharge continues in this condi...

Page 14: ...OLLECTOR CONNECTOR 2 AC INPUT FAIL 3 UPS ON 4 GROUND 5 LOW BATTERY 6 UPS SHUTDOWN 7 UPS SHUTDOWN 8 9VDC RS232 CONNECTOR 1 DCD 2 TX 3 RX 4 DTR 5 SIGNAL GROUND 6 DSR 7 CTS 8 RTS SIGNAL OPEN COLLECTOR CO...

Page 15: ...ature Controlled Reversible Forced Air Dimensions See Model Selection Guide Weight See Model Selection Guide DESIGN Standard Features Power Factor Corrected Digital Regenerative On Line Sinewave Inver...

Page 16: ...s 1000 700 1250 875 1500 1050 2000 1400 Input Current Amps 120VAC 7 2 8 8 10 7 14 3 Output Current Amps 8 3 10 4 12 5 16 7 Input Plug Standard NEMA Type 5 15P 5 15P 5 15P 5 20P Battery Backup Time Min...

Page 17: ...lectrolyte is harmful to the skin and eyes It may be toxic CAUTION A battery can present a risk of electrical shock and high short circuit current The following precautions should be observed when wor...

Page 18: ...tory In consulting the factory always have the unit model number and serial number at hand This information is located on the identification label and is essential in retrieving your unit s performanc...

Page 19: ...ive carrier available or via customer s shipping instructions 2 3 The nature of certain equipment installations may be such that it would be impractical or technically infeasible to remove the Clary p...

Page 20: ...362 8908 Circuit Breaker 363 11043 AC Output Lamp 362 8495 Fuse 15 Amp 250VAC 171 9519 Handle 120 12535 2 Filter Assembly LEVEL II PART NO DESCRIPTION 360 9307 4 Output Terminal Block 4 Position 360 9...

Page 21: ...ff by the Load On Off switch on the Front panel The Internal Hard Bypass is protected by the Input Circuit Breaker See System Schematic 118 14052 WARNING Whenever UPS has utility power on the input an...

Reviews: