background image

T H E   C O N T I N U O U S   P O W E R   C O M P A N Y

Page 13

OPERATION

Nce the system has been properly installed,
it is ready to operate. The following
procedures will explain how to start-up the

system while plugged into rated electrical power.

Normal Operation on AC Start-Up:

  Be sure the power cord is plugged into an

appropriately rated outlet.

 Activate the 

INPUT ON/OFF

 Circuit Breaker to

the 

“ON”

 position.

 Activate the 

SYSTEM ON/OFF

 Switch to the

“ON”

 position.

The system will go through a diagnostic test routine
and test all the L.E.D.s.

 The green 

AC INPUT

 light will flash several

times before it illuminates steady state.

  At least four green 

BATTERY

 lights illuminate.

  The audible alarm will sound a short burst.

  Push and hold in the 

AC OUTPUT ON/OFF

Switch for at least two seconds.

 The 

AC OUTPUT

 neon indicator, in the center

of the panel, will illuminate indicating output
power is available at the rear panel outlets and
the Inverter is operating.

Battery Test Operation:

Switch the 

INPUT ON/OFF

 Circuit Breaker 

“OFF”

.

This will simulate a power loss to test battery
operation.

 The 

green 

AC INPUT

 light will flash every two to

three seconds.

 The 

red 

BATTERY ON

 light illuminates.

  An intermittent audible alarm will sound.  (The

SILENCE

 Switch may be operated at this time, it

must be held in for at least 2 seconds to quiet
the alarm.)

  As battery discharge continues in this condition,

the five green 

BATTERY

 L.E.D.s will start to

shut off.  Each light represents approximately
20% of the battery reserve available.  If this
were to continue until all four lights shut off, the
last green light will flash, indicating that a LOW
BATTERY situation is present and system
shutdown is imminent.  The intermittent alarm
will become continuous at this point.  The UPS
will automatically shut itself off to avoid
excessive battery discharge within the next two
minutes.  When power returns, normal operation
of the UPS resumes without any operator
adjustment.

The duration of actual battery backup time and the
LOW BATTERY condition varies depending on the
amount of load, charge on the battery, and condition
of the battery.  The condition of the battery may be
checked provided two conditions are satisfied:

1.  AC power is present at the input of the

unit.

2.  The battery is fully charged.

To check the battery:

  Push and hold the 

TEST

 switch in for at least

two seconds.

 The 

red 

REPLACE

 light will flash.

 The 

red 

BATTERY

 light will light.

The microprocessor will run a battery diagnostic
check.

  The audible alarm will sound after the test.

 The 

red 

BATTERY

 light will turn off.

O

Summary of Contents for SN1000

Page 1: ...of Clary Corporation is proprietary confidential and not to be disclosed disseminated or used except for the purpose provided by CLARY CORPORATION P N 510 12580 A RD 12 29 03 Manufactured by T H E C...

Page 2: ...LE PAGE TABLE OF CONTENTS 1 INTRODUCTION 3 TECHNICAL DESCRIPTION 4 PACKAGING 6 PHYSICAL DESCRIPTION 7 SUMMARY OF INDICATORS AND CONTROLS 11 INSTALLATION 12 OPERATION 13 SIGNALS AND INTERFACING 14 SPEC...

Page 3: ...nance of the UPS and batteries Be aware of the following symbols and their meaning as they appear throughout the manual This equipment generates and uses radio frequency energy and if not installed an...

Page 4: ...owing exactly what patterns the supply utility power maintains and by knowing exactly the condition and life expectancy of the battery reserve Reference the block diagram for a simplified explanation...

Page 5: ...NE EMERGENCY CUTOFF SWITCH VOLTAGE WINDOW DETECTOR COMMON MODE CHOKE RECTIFIER CHARGER POWER FACTOR CORRECTOR DC RAILS MICROPROCESSOR CONTROLLER AC INVERTER GENERATOR LOAD STANDBY BATTERY COMMON MODE...

Page 6: ...it report this to your carrier These units are encapsulated in a protective wrap that comes apart once the product is removed from the shipping carton Save all packing material for future use Take ext...

Page 7: ...nhanced to ensure you have a full understanding of the operation of this system Visual indicators used on the front panel are long lasting very efficient light emitting diodes LED When operating the p...

Page 8: ...rating indicator 11 Bypass indicator 4 Battery Level Charge discharge indicators 12 Alarm Silence switch 5 Load Level Output capacity indicators 13 Fault indicator 6 Cold Start DC start switch 14 Batt...

Page 9: ...IGNAL Open collector signal contacts 17 INPUT Dual pole circuit breaker 21 RS232 Computer communications signals 18 DC INPUT Auxiliary battery connector 22 IDENTIFICATION LABEL 19 SYSTEM OUTPUT 120VAC...

Page 10: ...l Rear Panel Callouts 16 INPUT Terminal Block 3 position 20 Signal Open collector signal contacts 17 INPUT BREAKER Dual pole circuit breaker 21 RS232 Computer communications signals 18 DC input Auxili...

Page 11: ...tility voltage is available it may still be a requirement to initialize some equipment When this switch is pressed in for at least two seconds the system will start up on battery power The SYSTEM ON O...

Page 12: ...o be stored it is recommended to refresh the internal battery at least once every 90 days To do this plug the system in position the power On Off switch to ON press and hold at least two seconds the L...

Page 13: ...nates An intermittent audible alarm will sound The SILENCE Switch may be operated at this time it must be held in for at least 2 seconds to quiet the alarm As battery discharge continues in this condi...

Page 14: ...OLLECTOR CONNECTOR 2 AC INPUT FAIL 3 UPS ON 4 GROUND 5 LOW BATTERY 6 UPS SHUTDOWN 7 UPS SHUTDOWN 8 9VDC RS232 CONNECTOR 1 DCD 2 TX 3 RX 4 DTR 5 SIGNAL GROUND 6 DSR 7 CTS 8 RTS SIGNAL OPEN COLLECTOR CO...

Page 15: ...ature Controlled Reversible Forced Air Dimensions See Model Selection Guide Weight See Model Selection Guide DESIGN Standard Features Power Factor Corrected Digital Regenerative On Line Sinewave Inver...

Page 16: ...s 1000 700 1250 875 1500 1050 2000 1400 Input Current Amps 120VAC 7 2 8 8 10 7 14 3 Output Current Amps 8 3 10 4 12 5 16 7 Input Plug Standard NEMA Type 5 15P 5 15P 5 15P 5 20P Battery Backup Time Min...

Page 17: ...lectrolyte is harmful to the skin and eyes It may be toxic CAUTION A battery can present a risk of electrical shock and high short circuit current The following precautions should be observed when wor...

Page 18: ...tory In consulting the factory always have the unit model number and serial number at hand This information is located on the identification label and is essential in retrieving your unit s performanc...

Page 19: ...ive carrier available or via customer s shipping instructions 2 3 The nature of certain equipment installations may be such that it would be impractical or technically infeasible to remove the Clary p...

Page 20: ...362 8908 Circuit Breaker 363 11043 AC Output Lamp 362 8495 Fuse 15 Amp 250VAC 171 9519 Handle 120 12535 2 Filter Assembly LEVEL II PART NO DESCRIPTION 360 9307 4 Output Terminal Block 4 Position 360 9...

Page 21: ...ff by the Load On Off switch on the Front panel The Internal Hard Bypass is protected by the Input Circuit Breaker See System Schematic 118 14052 WARNING Whenever UPS has utility power on the input an...

Reviews: