 ASSISTANCE 

If you have trouble charging the battery, the battery alarm is active and your electronic device connected to the e-Power IP is 
not powered because the battery voltage is too low. Please follow the procedure below: 

 

1.  Please follow the procedure « Turbine Check Cycle » (see chapter « How do you check if the e-Power IP runs 

properly? » Annex: Quick Start Instruction LIN036ST). 

a. 

If the turbine does not provide enough AC voltage, please follow the point 2 below. 

b. 

If the solenoid does not activate, please contact CLA-VAL. 

 

2.  Please follow the procedure of chapter « What is the differential pressure across the turbine » annex: Quick Start 

Instruction LIN036ST). 

a.  If you do not reach 6 meters differential pressure across the turbine (185 VAC), please read on the graph (chapter 

« What is the differential pressure across the turbine » Annex: Quick Start Instruction LIN036ST) the real power 
provided by the turbine and finally check that your power balance is positive. 

b. 

If the turbine provides no AC voltage, please follow the point 3 below. 

 

3. 

Close the bypass ball valve, disconnect the 2 removable terminals at the same time by pulling with 2 fingers (see page 
1 of Annex: Quick Start Instruction LIN036ST), With the help of the ohmmeter, measure the resistance of the 3 phases 
of 210 ± 10 ohm on the terminal of the PCB (see chapter 2.4 PCB). 3 measurements must be taken: between the cable 
pairs: Brown and Black / Brown and Grey / Black and Grey.

 

a.  If you don’t measure 210 ± 10 ohm, the connection between the generator and the PCB is wrong. Contact CLA-

VAL  

b. 

If you measure the good value, proceed to point 4. 

 

4. 

If during point 1 and 2, the turbine does not provide any voltage, you measure 3 times 210 ohm and you are sure that 
the inlet/ outlet ball valves are open, isolate the e-Power IP, purge through the Serto connection of the solenoid on the 
e-Power IP. Unscrew the 4 screws 5 of the generator to the body of the turbine. 

When the generator is separated from the body, you have the opportunity to check the turbine wheel as shown on the 
picture below. It is possible that the wheel does not rotate, due to the dirt etc. Clean the wheel to be sure that the water 
can flow properly through the turbine. 

 

 

 

 

 

 

 

 

 

 

If other troubles occur, please contact the technical support through the internet website: 

www.cla-val.ch

 

Summary of Contents for e-Power IP

Page 1: ...urbine Power 14 W Voltage 12 V and 24 V CLA VAL Europe www cla val ch cla val cla val ch 1 LIN036UE 10 13 Copyright CLA VAL Europe Specifications subject to change without notice no contractual illust...

Page 2: ...2 e Power Ip properties 5 2 1 Performance 5 2 2 Description 6 2 3 Technical Data 8 2 4 PCB 9 2 5 Battery Properties 10 2 6 Battery Alarm 10 3 Commissioning 10 3 1 Mounting Instructions 10 3 2 Quick S...

Page 3: ...ing valve on the valve bypass before connecting the battery to the PCB 1 3 DIAGNOSTIC FOR THE LED The LED is located on the PCB in the electrical box 1 4 GENERAL DISCLAIMER In accordance with our poli...

Page 4: ...V V V V V V V V I I I V P I V P P P I V P The electric current on the load is 2x higher at at 12V than at 24 V for the same power Power balance Power balance Power generated Power supplied plied plied...

Page 5: ...e battery delivers the following output voltage current and power Output voltages Amps continous 60 min h Amps peak 1 min h 12 V 1 16 A 14 W 5 A 60 W 24 V step up 0 58 A 14 W 2 0 A 48 W The electrical...

Page 6: ...cations subject to change without notice no contractual illustrations 2 2 DESCRIPTION Electrical box factory supplied Silicat gel crystal sachet Wall mounting kit Quick Start Instructions No LIN036ST...

Page 7: ...erator Filter for solenoid Terminal for the solenoid and the cable to the electrical box do not attempt to open the product as this will invalidate the warranty Hydraulic output Differential pressure...

Page 8: ...1 min h 5 A 60 W Output 24 VDC step up A continuous 60 min h 0 58 A 14 W A high peak 1 min h 2 5 A 60 W Battery alarm output Dry contact switch Operating display Charging LED flashes red Discharging L...

Page 9: ...rt Instruction LIN036ST in the Annex Terminal Turbine 2 option Terminal No Code Function Color 1 L1 Phase 1 Black 2 L2 Phase 2 Brown 3 L3 Phase 3 Grey 4 No connection Terminal Turbine 1 Terminal No Co...

Page 10: ...standard 12 V 7 0 Ah option 2 6 BATTERY ALARM The dry contact battery alarm on connections 5 and 6 of terminal 3 allows transmission via a SCADA system The dry contact is closed when the battery volt...

Page 11: ...RE 4 1 INSTALLATION OF DRIVER USB Refer to the driver USB installation manual LIN006UE 4 2 SOFTWARE FIRMWARE UPDATE For Software updates please refer to our web site www cla val ch a Select Download b...

Page 12: ...ecommended not to change the values Factory Values according the table below Otherwise the proper use of the e Power IP cannot be guaranteed When the computer connection cable to the PCB is disconnect...

Page 13: ...scharging current Automatic Start turbine Low Battery Level V Low level battery Used to restart the turbine 12 0 V Default value Start Temporisation High Battery level V High battery level is used to...

Page 14: ...cording to the battery capacity 3 Click Write parameters 4 The battery capacity change is completed 4 7 FORCED CHARGE MODIFICATION The forced charge period can be modified to allow for periods where t...

Page 15: ...your power balance is positive b If the turbine provides no AC voltage please follow the point 3 below 3 Close the bypass ball valve disconnect the 2 removable terminals at the same time by pulling wi...

Page 16: ...n the system by disconnecting the wires connected to the battery 4 Unscrew the 4 nuts for the fixing of the battery 5 Replace the battery 6 Screw the 4 nuts to fix the new battery Don t screw the batt...

Page 17: ...ntion to its orientation during the assembly The diaphragm is drilled to allow the water to pass through Please align the hole drilled in the body the hole drilled in the cover and the hole in the dia...

Page 18: ...vous que le robinet du by pass soit ferm pour arr ter la turbine L accumulateur doit tre d connect La LED sur la carte lectronique ne doit pas clignoter Output voltage 12 VDC Terminal 1 12 VDC and te...

Page 19: ...ment Fermez le coffret lectrique l aide des 6 vis La e Power IP est mise en service et pr te l emploi How do you check if the e Power IP run properly Comment v rifier le bon fonctionnement de la e Pow...

Page 20: ...noid connector using a screwdriver Enlevez le connecteur de l lectrovanne l aide d un tournevis croix Switch the solenoid with a 9 V 6LR61 battery like the picture to engage the turbine Commutez l lec...

Page 21: ...onna tre la puissance d livr e par votre e Power IP afin d valuer votre bilan nerg tique Power consumptions available Consommations lectrique admissibles Horizontal mounting Montage horizontal 16 Watt...

Reviews: