24

 

OPERATION 

 

 

3)  Other setups (SW4) 

Using  this  switch,  specify  whether  to  hold  or  clear  the  output  when  an  error  occurs  and 
whether this slave station is the end station (station furthermost from the master station) or 
not. 

 

Position 

 

Switch 

No. 

Function 

OFF 

ON 

 

No.1 

Specifies  whether  to  hold  or  clear  the 
output  when  an  error  (bus  line  error, 
time-over, etc.) occurs. 

Clear 

Hold 

 

No.2 

Sets the end station. 
(110

Ω

-terminating resistor is built-in.) 

  Turn  OFF  this  switch  if  the 

CC-Link  special  high-performance 
cable  is  used.    (See  also  the  Fig. 
below.) 

In 

setting 

the middle 

station 

In 

setting the 

end station

 

1.  If a terminal resistor is connected externally (on a terminal block), 

be sure to set this switch to OFF. 

 

  End station settings when using the CC-Link special high-performance cable 

 

If  the  CC-Link  special  high-performance  cable  (FANC-SBH 
made  by  Kuramo  Denko,  etc.)  is  used  for  the  communication 
cable  and  this  slave  station  is  the  end  station,  always  turn 
OFF the end station setting (SW4 No. 2).    Additionally, 130

Ω

-terminating  resistor  (1/2W),  which  is  purchased  on  the  gen-
eral market or supplied with the master station, is connected 
to  a  position  between  the  terminal  blocks  DA  and  DB  of  this 
slave station to set the station to the end station. 

 

When connecting a resistor purchased on the general market, 
perform the insulation process so that the lead wires of the re-
sistor are not in contact with each other (short-circuit). 

 

    

 

 

If the switch is set with the power 

ON

, the setting contents may 

not be recognized.    Set the switch always with the serial transmis-
sion unit block power 

OFF

 

 

Set the terminal resistance correctly, referring to the 

Master Sta-

tion

  User

s  Manual.    If  the  terminal resistance  value  and  connec-

tion method are mistaken, there is a possibility that communication 
errors may occur. 

 

 

In  connecting  the  externally  mounted  terminal  resistor  at  the  out-
side, be sure to turn the terminal station setting 

OFF

 

 

Where  the  externally  mounted  terminal  resistance  is  connected  at 
the outside, proper insulation is required to prevent the resistor lead 
wire from contact (short-circuit). 

 

   

 

  

 

CAUTION

CAUTION

CAUTION

CAUTION 

  

 :

::

  

 

Switch No. 

バルブ

 

ユニット

 

In case of connecting the 
registance between DA and DB 

Summary of Contents for M4GA4-T6G1

Page 1: ...PE SERIAL TRANSMISSION TYPE SERIAL TRANSMISSION TYPE SERIAL TRANSMISSION TYPE M4G 4 M4G 4 M4G 4 M4G 4 T6G1 T6G1 T6G1 T6G1 Please read this instruction manual care fully before using this product parti...

Page 2: ...read this read this read this instruction instruction instruction instruction manual carefully for manual carefully for manual carefully for manual carefully for proper operation proper operation pro...

Page 3: ...ecifications 5 1 4 Outside view of valve 9 1 5 Slave station for valve 19 2 CAUTION 22 3 OPERATION 3 1 Switch setting 22 3 2 Correspondence between Output Nos and internal connector Nos 25 3 3 Corresp...

Page 4: ...programs that control these devices installed away from the master system has the following features 1 To a single master station the CC Link system allows the connection of up to 64 remote I O statio...

Page 5: ...tation Station controlling remote I O stations remote device stations and local stations Remote I O station Remote station that handles ON OFF data only Remote device station Remote station that handl...

Page 6: ...e1 Not required Degree of protection Dust proof Vibration shock m s2 50 or less 300 or less Atmosphere Use in the environment containing corrosive gas is not permissible Note 1 Use the turbine oil Cla...

Page 7: ...0 38 7 1 0 15 Rc3 8 G3 8 NPT3 8 3 position PAB connection 6 0 0 37 6 8 0 13 2 position 8 3 0 23 9 0 0 21 All ports closed 7 4 0 15 8 8 0 19 ABR connection 7 5 0 15 9 5 0 21 M4GB4 Rc1 2 G1 2 NPT1 2 3 p...

Page 8: ...on speed In the case of multi drop connection Ver 1 10 B RATE Transmission Speed Interstation Cable Length Total Cable Extension 4 10Mbps 100m 3 5Mbps 160m 2 2 5Mbps 400m 1 625kbps 900m 0 156kbps 0 2m...

Page 9: ...xed use of cables only for CC Link and high performance cables only for CC Link is allowed 3 Slave station specification Item Specification Communication object CC Link Ver1 10 Note 1 Power supply vol...

Page 10: ...L1 26 5xn 129 5 144 5 26 5 pitch 24 5 Push in joint 4 A port Rc3 8 4 A port Mounting hole 4 6 6 Push in joint 2 B port Rc3 8 2 B port 2 Rc1 2 5 R port 2 Rc1 2 1 P port 2 Rc1 2 3 R port 17 35 35 19 5...

Page 11: ...joint 4 A port Rc3 8 4 A port Mounting hole 4 9 Push in joint 2 B port Rc3 8 2 B port 2 Rc1 2 5 R port 2 Rc1 2 1 P port 2 Rc1 2 3 R port 21 35 3 36 6 29 4 2 Rc1 8 12 14 PA port 29 39 1 51 9 131 9 Manu...

Page 12: ...id 137 7 L1 26 5xn 135 5 179 26 5 pitch 59 Push in joint 2 B port Rc3 8 2 B port 131 9 Manual override position 121 6 Manual override position 111 2 Manual override position 40 49 5 33 31 6 117 2 Rc3...

Page 13: ...5 pitch 59 Push in joint 4 A port 2 Rc1 8 82 84 PR port Mounting hole 4 9 Rc3 8 2 B port 131 9 Manual override position 121 6 Manual override position 111 2 Manual override position 40 49 5 33 31 6 1...

Page 14: ...noid 137 7 143 26 5 pitch Push in joint 4 A port 2 Rc3 8 5 R port Mounting hole 4 6 6 Push in joint 2 B port 131 9 Manual override position 121 6 Manual override position 111 2 Manual override positio...

Page 15: ...le solenoid 137 7 149 29 pitch Mounting hole 4 9 Rc1 2 4 A port 131 9 Manual override position 121 6 Manual override position 111 2 Manual override position 29 49 5 33 27 16 5 103 7 61 141 5 L1 29xn 1...

Page 16: ...9 Mounting hole 4 9 2 Rc1 2 5 R port 2 Rc1 2 1 P port 2 Rc1 2 3 R port 21 35 3 43 8 29 4 2 Rc1 8 12 14 PA port 29 39 1 51 9 131 9 Manual override position 121 6 Manual override position 111 2 Manual o...

Page 17: ...Double solenoid 137 7 L1 26 5xn 128 5 169 26 5 pitch 49 Mounting hole 4 6 6 131 9 Manual override position 121 6 Manual override position 111 2 Manual override position 33 48 36 27 4 22 Push in joint...

Page 18: ...5 Single solenoid 207 1 Double solenoid 137 7 L1 29xn 133 179 29 pitch 59 Mounting hole 4 9 131 9 Manual override position 121 6 Manual override position 111 2 Manual override position 40 49 5 33 31...

Page 19: ...1 29xn 133 179 29 pitch 59 Push in joint 2 B port 2 Rc1 8 12 14 PA port Mounting hole 4 9 131 9 Manual override position 121 6 Manual override position 111 2 Manual override position 40 49 5 33 31 6 2...

Page 20: ...SM P00049 A 19 PRODUCT 1 5 Slave station for valve 1 Appearance 41 50 84 47 5 66...

Page 21: ...he user specifies a value out of range when setting the station number or transfer rate Lit again when the user corrects the setting and reboots the system Blinks when the station number or transfer r...

Page 22: ...ce Wiring connection to sta tion is accomplished through these terminal blocks Function of each terminal is printed on the face of station mounting device Choose 6 6mm wide or less of M3 crimp type te...

Page 23: ...ring an error and specifying the end station Since different switches are used for different kinds of setup you must correctly identify the switch to be used Before changing the switch positions be su...

Page 24: ...se the same station No 2 Transfer rate setting SW3 Set the transfer rate for communication between the master and slave stations Position Transfer rate 0 156kbps 1 625kbps 2 2 5Mbps 3 5Mbps 4 10Mbps B...

Page 25: ...2 Additionally 130 terminating resistor 1 2W which is purchased on the gen eral market or supplied with the master station is connected to a position between the terminal blocks DA and DB of this slav...

Page 26: ...and manifold solenoid correspond with each other as per tables posted below 2 Manifold block number is allocated from leftmost block toward right while holding piping port facing to you regardless th...

Page 27: ...the Mitsubishi User s Manual CC Link system master local units Functions particular to this slave station unit are the specification of the state of output during an error and the declaration of the...

Page 28: ...e name and specifications of the recommended cable in the table below Specifications Item Cable exclusively for CC Link High performance cable exclusively for CC Link Name FANC SB FANC SBH Manufacture...

Page 29: ...uit for the solenoid valve system Moreover two separate power sources can be used to supply power independently to the slave station unit and the solenoid valve system The illustrations below are exam...

Page 30: ...er power cables Since connecting the electric wires that were only twisted direct to the terminal strip may cause firing be sure to use a crimp terminal Connect the power supply always after checking...

Page 31: ...has blown The ERR LED on the master station unit blinks to report an error Check the unit associated with the register that is ON one among SW0098 through SW009B Is any of the special master station l...

Page 32: ...t Is the data cable properly con nected Y N N Y Is the L RUN LED lit Is the SD LED lit or blinking Is the transfer rate B RATE correctly set Y N N N Y Y Correct the power supply voltage The unit is fa...

Page 33: ...setting switches without a duplicate N Correct the station number setting Turn the power OFF and then ON Y The unit is faulty The station number setting switches are faulty Y Done From previous page...

Page 34: ...PAB connection Rc1 4 2 G1 4 2 NPT1 4 2 Rc3 8 G3 8 e Option NPT3 8 Rc1 2 2 none G1 2 2 External pilot NPT1 2 2 Coolant proof f Station number 2 M4GB4 only A B port filter integrated Supply spacer 2 st...

Reviews: