Page 20
1. The installation must conform to
local codes or in absence of local
codes, with the
National Fuel Gas Code, ANSI Z223.1 or
the CAN/CGA-B149, Installation Codes.
2. Check with utilities for proper gas pressure and gas supply line.
3. Check the altitude elevation of dryer.
4. The dryer and its individual shut-off valve must be disconnected
from the gas supply piping system at test pressures in excess of 1/
2 psig (.04 bar).
5. The dryer must be isolated from the gas supply piping system by
closing its individual manual shut-off valve during any pressure
testing of the gas supply piping system, at test pressures equal to
or less than 1/2 psig (.04 bar).
NATURAL GAS ONLY
Check the gas pressure inlet supply to the dryer, 11”w.c.
(27.4 bar) pressure maximum. Check the manifold pressure,
3.5”w.c. (8.8 bar) pressure inside the dryer.
CAUTION
Low gas pressure and intermittent gas will cause gas ignition
problems and inadequate drying of the clothes load.
GAS PIPING INSTALLATION
GAS PIPING
INSTALLATION
Summary of Contents for HD170
Page 12: ...Page 12 GAS DRYER DIMENSIONS ...
Page 13: ...Page 13 STEAM DRYER DIMENSIONS ...
Page 18: ...Page 18 GAS PIPING INSTALLATION ILLUSTRATION ...
Page 26: ...Page 26 DRYER INSTALLATION WITH MULTIPLE EXHAUST ILLUSTRATION ...
Page 33: ...Page 33 OPERATING INSTRUCTIONS TWO TIMER MODELS ...
Page 41: ...Page 41 DIRECT SPARK IGNITION OPERATION FLOW CHART ...
Page 43: ...Page 43 BURNER AIR INLET ADJUSTMENT BURNER AIR INLET ADJUSTMENT ...
Page 44: ...Page 44 BASKET ALIGNMENT FOR DRYERS WITH TM200 GEAR REDUCER ...
Page 53: ...Page 53 REAR VIEW TM200 GEAR REDUCER See following page for partnumbers ToGearM otor ...
Page 55: ...Page 55 REAR VIEW GEAR MOTOR See following page for partnumbers ToGearM otor ToFanM otor ...
Page 75: ...Page 75 ...