Page 25
DRYER INSTALLATION WITH MULTIPLE EXHAUST
For Exhaust Duct less than 14 feet (5 m) and 2 elbows
equivalent and less than 0.3 inches (.8 mbar) static pressure.
DRYER EXHAUSTS
Area of section “A-A” must be equal to the sum of dryer exhaust pipes
entering multiple exhaust pipe. (
See chart below.
)
MODELS:
HD150
No. of Dryers
Duct Diameter
(in inches)
(in CM)
1
2 3
4
5
6
7
8
9 10 11 12
12 17 21 24 27 30 32 34 36 38 40 42
30 43 53 61 68 76 81 86 91 97 100 106