Bonding and Grounding the Cisco MGX System
Figure C-2
Mixed Grounding System
Table C-1
Ground Point Descriptions for Mixed Grounding
Connection
Description
Z1
–48 VDC return.
Z2
Protective earth or safety ground (green/yellow).
Z3
Equipment ground for non-isolated equipment.
Z4
Equipment ground for isolated equipment.
Z5
Equalizing frame ground. This ground creates low-impedance equalization
between frames.
B
Battery ground.
1, 2, 3, 4
Connection points to the building’s ground system: a potential can exist
between these points within the ground system.
T
Common-mode EMI filters.
Battery A
Nonisolated equipment
– 48V-A
T
– 48V-A
– 48V-A
logic power
+
–
– 48V-B
1
1
B
2
B
T
T
Safety ground
Safety ground
Safety ground
– 48V-A RTN
– 48V-A
– 48V-A RTN
– 48V-B
– 48V-B RTN
– 48V-B
– 48V-B RTN
Safety ground
Battery B
– 48V-B
+
–
Isolated equipment
– 48V-A
logic power
– 48V-B
2
4
T
Z1
Z1
Z1
Z1
Z2
Z2
Z2
Z2
Z3
3
Z4
Z5
28311