58
RECmax-CVM
Instruction Manual
7�3�13�8� Sensitivity current I
Δ
n
The
Functions
0x04
and
0x10
are implemented for this variable�
Table 48:Modbus memory map: Sensitivity current
Sensitivity current I
Δ
n
Configuration variable
Address
Valid data margin
Default value
Sensitivity current
C361
0:
30 mA
1:
0�1 A
2:
0�3 A
3:
0�5 A
4:
1 A
0
7�3�13�9� Activation delay
The
Functions
0x04
and
0x10
are implemented for this variable�
Table 49:Modbus memory map: Activation delay
Activation delay
Configuration variable
Address
Valid data margin
Default value
Activation delay
C362
0:
INS curve
1:
SEL curve
2:
0�1 s
3:
0�2 s
4:
0�3 s
5:
0�4 s
6:
0�5 s
7:
0�75 s
8:
1�00 s
0
7�3�13�10� Reclosing sequence
The
Functions
0x04
and
0x10
are implemented for this variable�
Table 50:Modbus memory map: Reclosing sequence
Reclosing sequence
Configuration variable
Address
Valid data margin
Default value
Earth leakage reclosing
sequence
C368
0 ��� 14
(according to
DI
in
10
Circuit breaker reclosing
sequence
C369
0 ��� 8
(according to MA in
5
7�3�13�11� Configuration of the REC LOCKED and POSITIVE SAFE OUTPUT relays
The
Functions
0x04
and
0x10
are implemented for this variable�
Table 51:Modbus memory map: Configuration of the relays
Configuration of the REC LOCKED and POSITIVE SAFE OUTPUT relays
Configuration variable
Address
Valid data margin
Default value
Type of contact, REC LOCKED relay
C366
0: STD
, without positive safety
1: POS
, with positive safety
1
Type of contact, POSITIVE SAFE OUTPUT
relay
C367
0: STD
, without positive safety
1: POS
, with positive safety
1