6�2�6�- FACT: FACTORY CONFIGURATION
The factory default Configuration can be restored on this screen�
PROG
PROG
PROG
Press the
RESET
key to move between the different options:
NO
, the factory values are not restored�
YES
, the factory values are restored�
Selecting the option
YES
means a
total reset
, which includes the control parameters
for the protection trigger� Its use is therefore only advised when the downstream
loads are out of service�
Press the
PROG
key to save the selected option and exit the setup menu; when exiting, the screen in
is displayed for a few seconds�
If you do not press any key for 10 s, the screen in
appears and the device opens the
Delay
and Sensitivity
screen, without saving the changes made�
Default value: NO
6�3�- RS-485 COMMUNICATIONS: PERIPHERAL NUMBER
The peripheral number is configured in RS-485 communications by holding the
PROG
key down for
more than 3 seconds while the current value is displayed�
The
td s
A
I n
REC
+
PROG
N
symbol appears on the display and the value can be changed�
PROG
PROG
Press
RESET
to increase the value, or
PROG
to decrease it�
Hold the PROG key down for more than 3 seconds to save the configured value, in which case the
td s
A
I n
REC
+
PROG
N
symbol disappears from the display�
The device does not save the changes and the
td s
A
I n
REC
+
PROG
N
symbol disappears from the display if no key
is pressed for 10 seconds�
Minimum configuration value: 0
Maximum configuration value: 255