61
Instruction Manual
RECmax-CVM
Circuit breaker protection
Rated current (In)
6 - 10 - 16 - 20 - 25 - 32 - 40 - 50 - 63 A ~
Rated voltage (Un)
240 / 415 V
~
Magnetic trip curves
C / D
Cross-section
Flexible cable
Rigid cable
25 mm
2
35 mm
2
Number of poles
RECmax-CVM 2-pole
RECmax-CVM 4-pole
2
4
Maximum torque
4�5 Nm
Residual earth leakage current
0�851
I
∆
n
Breaking capacity (EN 60898)
Poles
Voltage
Icn / Ics
1 - 4
230 / 400 V
6 kA
Breaking capacity (EN 60947-2)
Poles
Voltage
Icu / Ics
2
< 125 V
30 kA
Breaking capacity (EN 60947-2)
~
Poles
Voltage
Icu
2
127 V
30 kA
240 V
20 kA
415 V
10 kA
4
240 V
20 kA
415 V
10 kA
Automatic reclosing
Successive attempts by earth leakage
programmable (by default: 10)
Successive attempts by circuit breaker
programmable (by default: 2)
Timer between successive attempts
programmable (by default: 3 min�)
Meter reset time after last reclosing
programmable (by default: 30 min�)
Inputs: EXT ON/OFF and EXT LOCKED
Type
Voltage-free
Insulation
Double insulation
Outputs REC LOCKED and POSITIVE SAFE OUTPUT alarms
Type
Solid-state relay
Maximum voltage
230 V ~
Maximum current
100 mA
Maximum power
500 mW
Digital Output
Type
NPN optoisolated transistor
Maximum voltage
24 V
Maximum current
50 mA
Maximum frequency
16 imp/s�
Pulse width
30 ��� 500 ms (programmable)
BREAKER ON/OFF output
Type
Microswitch
Maximum voltage
230 V ~
Maximum current
0�5 A
Maximum power
60 VA
Installation category
CAT III 300V