Instruction Manual
RECmax-CVM
Table 30:Format of the variable: Power status�
Bit
1
1:
Status of main switch OFF
2
1: EXT ON/OFF
input
3
1: EXT LOCKED
input
4
1:
Earth leakage transformer error
5
1: RESET
key activated
6
1: TEST
key activated
7
1: PROG
key activated
8
1:
Manual locking deactivated
9
EXT LOCKED
input activated
7�3�8� STATUS OF THE RELAY OUTPUTS
All Modbus map addresses are expressed in hexadecimal�
The
Function 0x04
is implemented for these variables�
Table 31:Modbus memory map: Status of the relay outputs�
Parameters
Address
Valid data margin
Status of the outputs
C390
-
The format of the variable is shown in
Table 32:Format of the variable: Relay status�
Bit
0
1: REC LOCKED
relay ON
1
1: POSITIVE SAFE OUTPUT
relay ON
7�3�9� DIGITAL OUTPUT STATUS
All Modbus map addresses are expressed in hexadecimal�
The
Function 0x04
is implemented for these variables�
Table 33:Modbus memory map: Digital output status�
Parameters
Address
Valid data margin
Digital output status
4E21
0x00:
Digital output OFF
0x04:
Digital output ON
7�3�10� POWER STATUS
All Modbus map addresses are expressed in hexadecimal�
The
Function 0x04
is implemented for these variables�
Table 34:Modbus memory map:
Power status�
Parameters
Address
Valid data margin
Power status
07D1
-
The format of the variable is shown in