-- Supply network analyzer CVM-144 (HAR) ----- User's manual --- Page No. 39
-
For passing to the next option, press "
display
": the setup for the second
output will
appear (
only if this output is available
).
dA 2
OUTPUT D/A Nr.2
code
xxxx
Proceed as in the previous sections.
1.- Output calculation:
)
.
(
)
20
(
Re
Offset
scale
F
Zero
solution
−
−
=
Offset & f. scale
= defined by the user
Zero
= 0 mA or 4 mA
(
)
Zero
Offset
Mesure
solution
mA
+
−
=
*
Re
mV = mA x ohms
mV
(100 ohms)
= mA x 100
- Maximum load is of 500
Ω
(10 V - 20 mA)
)
Output of the power factor parameter ( PF):
0/4 mA ----------------------------------------------------- 20 mA
+0.00 Ind. / 1.00 / Cap. – 0.00
ó
–0.00 Cap. / 1.00 / Ind. + 0.00