5�4�- CONNECTION AND RECLOSING TIME
In this point the action times of the device are configured in seconds:
Ton
is the minimum time between the connection and disconnection of a single stage.
TREC
is the maximum time between the disconnection and connection of a single stage.
TREC
must be greater than
ToN
; ideally, it should be 5 times greater.
Press the
key to enter edit mode. It is identified by the
symbol and the flashing of the
digits to be modified.
The
key increases the digit value.
The
key reduces the digit value.
The
key skips to the previous digit and the
key skips to the next digit.
Press
to validate the data; the
symbol disappears from the display.
Ton
:
Maximum value:
999.
Minimum value:
4.
Trec
:
Maximum value:
999.
Minimum value:
20.
If the value entered is lower than the minimum value or higher than the maximum value, the backlight
of the display flashes and the value entered is replaced with the minimum or maximum value, or with
the last value validated.
Press the
key to access the next programming step.
If no keys are pressed for 5 minutes, the device switches to the simulation screen,
.
77