Table 39 (Continuation): Modbus memory map: programming variables (Table 24)
Enabling alarms
Configuration variable
Address
Valid data window
Default value
Enable Alarm E13
1161
0
Enable Alarm E14
1162
0
Enable Alarm E15
1163
0
Enable Alarm E16
1164
0
Enable Alarm E17
1165
0
Output associated with Alarm E01
1170
0 (No),
1 (Alarm relay),
2 (Digital output 1)
2 (Digital output 2)
0
Output associated with Alarm E02
1171
0
Output associated with Alarm E03
1172
0
Output associated with Alarm E04
1173
0
Output associated with Alarm E05
1174
0
Output associated with Alarm E06
1175
0
Output associated with Alarm E07
1176
0
Output associated with Alarm E08
1177
0
Output associated with Alarm E09
1179
0
Output associated with Alarm E10
1179
0
Output associated with Alarm E11
117A
0
Output associated with Alarm E12
117B
0
Output associated with Alarm E13
117C
0
Output associated with Alarm E14
117D
0
Output associated with Alarm E15
117E
0
Output associated with Alarm E16
117F
0
Output associated with Alarm E17
1180
0
C
.-
Deleting parameters
Parameters can be deleted using
Function 05
: writing a relay.
Table 40:Modbus memory map: deleting parameters
Deleting parameters
Action
Address
Value to be sent
Deleting maximum values
200
FF
Deleting minimum values
210
FF
Deleting maximum and minimum values
220
FF
Deleting energies
230
FF
Deleting the stage search and stage enabling values of the leakage current alarm
240
FF
Deleting the no. of operations of all the relays
250
FF
Resetting alarms E14 and E15
260
FF
Restoring the default configuration values
300
FF
69
Instruction Manual
Computer SMART III
Summary of Contents for Computer SMART III 12
Page 1: ...INSTRUCTION MANUAL M015B01 03 21A REACTIVE ENERGY REGULATOR Computer SMART III...
Page 2: ...2 Computer SMART III Instruction Manual...
Page 110: ...9 CE CERTIFICATE 110 Computer SMART III Instruction Manual...
Page 111: ...111 Instruction Manual Computer SMART III...
Page 112: ...112 Computer SMART III Instruction Manual...