5.- CONFIGURATION
The various configuration parameters of the device can be consulted and edited in the device setup
menu.
The device always keeps the capacitors disconnected (except in the Plug&Play function).
This status is identified by the
symbol in the device status area of the display (
).
To access the setup menu, long keystroke the
key (> 3 s).
The Password screen appears on the display. The password to be entered is a combination of keys:
. It is unique and cannot be configured.
If it is not entered correctly, the device returns to the previous measurement screen.
If it is entered correctly and capacitors are connected, the disconnection screen appears.
Disconnection screen: used for the device to automatically disconnect all the stages before entering
the configuration.
While in this screen, the device does not respond to the keypad.
The device automatically exits this screen, and this can take a certain amount of time.
71
Instruction Manual
Computer SMART III