Press
to validate the data; the
symbol disappears from the display.
Press the
key to access the next programming step.
If no keys are pressed for 5 minutes, the device switches to the simulation screen,
“
”
.
5�8�- PROGRAM
The device is made up of stages with different powers. The base power (value 1) will be that of the
stage with the lowest power. The powers of all the other stages will depend on the power of the first
stage.
Example:
Program 1�1�1�1
, all the stages have the same power as the first one.
Program 1�2�4�4
, the second stage has twice the power and the next ones have four times the power
of the first one. (
See
)
When configuring the program, remember that the subsequent stage cannot be lower than the prior
stage, and that the first stage is always 1.
Press the
key to enter edit mode. It is identified by the
symbol and the flashing of the
digits to be modified.
The
key increases the digit value.
The
key reduces the digit value.
The
key skips to the previous digit and the
key skips to the next digit.
Press
to validate the data; the
symbol disappears from the display.
Minimum value:
1.1.1.1
Maximum value:
1.9.9.9
Press the
key to access the next programming step.
If no keys are pressed for 5 minutes, the device switches to the simulation screen,
.
81
Instruction Manual
Computer SMART III
Summary of Contents for Computer SMART III 12
Page 1: ...INSTRUCTION MANUAL M015B01 03 21A REACTIVE ENERGY REGULATOR Computer SMART III...
Page 2: ...2 Computer SMART III Instruction Manual...
Page 110: ...9 CE CERTIFICATE 110 Computer SMART III Instruction Manual...
Page 111: ...111 Instruction Manual Computer SMART III...