The device will respond to us with the next frame:
Address
Function
Initial
Register
Register
no�
CRC
01
10
03E8
0001
CRC
Note:
The values are shown in hexadecimal.
The number of registers to write must be the same as the size of the variable that is being
accessed.
It is possible to write several consecutive addresses, if the request meets the correct format.
7�2�3�- VARIABLES MODBUS
All
MODBUS
map addresses are hexadecimal.
7�2�3�1�- Energy
The
Read
function is implemented for these variables.
Table 16: Modbus variables: Energy (Table 1)�
Description
Address
Size
Units
Total values
Imported active energy
0x0000
32 bits
Wh
Exported active energy
0x0002
32 bits
Wh
Q1 reactive energy
0x0004
32 bits
varh
Q2 reactive energy
0x0006
32 bits
varh
Q3 reactive energy
0x0008
32 bits
varh
Q4 reactive energy
0x000A
32 bits
varh
Partial values
Partial imported active energy
0x0030
32 bits
Wh
Partial exported active energy
0x0032
32 bits
Wh
Q1 partial reactive energy
0x0034
32 bits
varh
Q2 partial reactive energy
0x0036
32 bits
varh
Q3 partial reactive energy
0x0038
32 bits
varh
Q4 partial reactive energy
0x003A
32 bits
varh
shows energies per tariff, only visible for the
CEM-C31-485-DS
model with the Tariff
option selected.(See
Table 17: Modbus variables: Energy (Table 2)�
Description
Address
Size
Units
Tariff 1
Tariff 2
Total values
Imported active energy
0x0100
0x010C
32 bits
Wh
Exported active energy
0x0102
0x010E
32 bits
Wh
Q1 reactive energy
0x0104
0x0110
32 bits
varh
Q2 reactive energy
0x0106
0x0112
32 bits
varh
Q3 reactive energy
0x0108
0x0114
32 bits
varh
Q4 reactive energy
0x010A
0x0116
32 bits
varh
43
Instruction Manual
CEM-C31
Summary of Contents for CEM-C31-485-DS
Page 2: ...2 CEM C31 Instruction Manual...
Page 52: ...11 CE CERTIFICATE 52 CEM C31 Instruction Manual...
Page 53: ...53 Instruction Manual CEM C31...
Page 54: ...54 CEM C31 Instruction Manual...
Page 55: ...55 Instruction Manual CEM C31...
Page 56: ...56 CEM C31 Instruction Manual...
Page 57: ...57 Instruction Manual CEM C31...