6�- CONFIGURATION
The
CEM-C31
have 2 configuration menus:
Metrologically relevant parameters configuration menu.
General configuration menu.
6.1.-
RELEVANT PARAMETERS CONFIGURATION
The most relevant parameters in metrological terms are configured in the programming menu.
Short press the
button to access this menu.
This button is sealable, see
“
”,
to restrict access to the programming
procedures.
The standby mode is activated again when no button is pressed for 60 seconds or by short
pressing the
button.
6�1�1� VOLTAGE PRIMARY TRANSFORMATION RATIO
This is the home screen for entering the voltage primary ratio.
Long press the
button to view the value to be programmed.
To write or modify the value, short press the
button
repeatedly, increasing the value of the flashing digit.
When the desired value is shown on the screen, move onto the next digit with a long press on
the
button, allowing the remaining values to be modified.
To validate the data, move to the last digit and long press the
button; the validation screen
will appear (
) indicating that the setup value has been saved.
Figure 16: Validation screen�
29