7.9.- TRANSFORMER CONFIGURATION
Note:
This screen is not visible on the
“slave”
devices.
The transformers that will be installed with the device are configured in this screen,
:
Figure 78: Configuration screen: Transformer configuration.
●
Num transformers
The number of transformers that will be installed is configured with this parameter, the options are:
2.
This option can only be used on the 3-wire model,
AFQm-3WF-xxxx
3.
With the option of
2
transformers, you should install a transformer measuring the L1
phase and another measuring the L2 phase. The L3 phase is left without a measuring
transformer.
In three-phase mains with neutral, 3 transformers are needed to ensure the correct
operation of the device.
●
Position
The location of the transformers is configured with this parameter, the options are:
LOAD
: If the transformers are installed in the load area, downstream from the
AFQm
.
MAINS
: If the transformers are installed in the mains area, upstream from the
AFQm
.
●
Ratio
The transformer ratio is configured with this parameter, i.e., the ratio between the transformer primary
and secondary.
Range of values:
Minimum value:
5 A
Maximum value:
5000 A
Summary of Contents for AFQm
Page 2: ...2 AFQm...
Page 3: ...3 AFQm CONTENIDO CONTENTS MANUAL DE INSTRUCCIONES 4 INSTRUCTION MANUAL 117...
Page 114: ...114 AFQm Manual de Instrucciones ESPA OL 14 CERTIFICADO CE...
Page 115: ...115 Manual de Instrucciones AFQm ESPA OL...
Page 116: ...116 AFQm Manual de Instrucciones ESPA OL...
Page 227: ...227 Instruction Manual AFQm ENGLISH 14 CE CERTIFICATE...
Page 228: ...228 AFQm Instruction Manual ENGLISH...