The phase balancing option in
AFQm-3WF-xxxx
works in unbalances produced by loads
connected between phases in three-phase mains without neutral. The
AFQm-3WF-xxxx
does not compensate unbalances produced by single-phase loads connected between
phase and neutral. Use a
AFQm-4WF-xxxx
to correct this type of unbalances.
Priority
Enable this option so that the device prioritises the functions in case of filter current saturation due to
overload:
With the function
enabled
, the current balancing between phases and the reactive current compensa-
tion is prioritised over the harmonic filtering.
With the function
disabled
, priority is given to the current harmonic filtering and power factor correc-
tion and overload balancing are penalised.
Table 24: Order of priorities
Priority
Order of priorities function
Disabled
Enabled
+
Harmonic filtering
Phase balancing
Power factor correction
-
Phase balancing
Power factor correction
Harmonic filtering
Reactive
Enable this function so that the device compensates the reactive energy or corrects the displacement
power factor, cos
Φ
.
Press the
key to access the next configuration step
Press the
key to access the main screen of the device without saving the configuration values
Summary of Contents for AFQm
Page 2: ...2 AFQm...
Page 3: ...3 AFQm CONTENIDO CONTENTS MANUAL DE INSTRUCCIONES 4 INSTRUCTION MANUAL 117...
Page 114: ...114 AFQm Manual de Instrucciones ESPA OL 14 CERTIFICADO CE...
Page 115: ...115 Manual de Instrucciones AFQm ESPA OL...
Page 116: ...116 AFQm Manual de Instrucciones ESPA OL...
Page 227: ...227 Instruction Manual AFQm ENGLISH 14 CE CERTIFICATE...
Page 228: ...228 AFQm Instruction Manual ENGLISH...