185
Instruction Manual
AFQm
ENGLISH
Range of values:
Minimum value:
0 A
Maximum value:
5000 A
●
Current limit
This parameter allows the maximum power of the active filter to be limited. The value is configured as
a percentage with respect to the device’s rated power.
Range of values:
Minimum value:
20%
Maximum value:
100%
Press the
key to access the next configuration step
Press the
key to access the main screen of the device without saving the configuration values.
7.7.- cos
Φ
Note:
This screen is not visible on the
“slave”
devices.
The device has two reactive power compensation modes (
Figure 76: Configuration screen: cos
Φ
(Mode 1 and Mode 2).
●
Mode 1
In this mode, cos
Φ
is set to a fixed value. The device will attempt to ensure that the reactive power on
the mains side corresponds to the specified cos
Φ.
Range of values:
0.7... -0.7
●
Mode 2
In this mode, two limits are defined to form an acceptance range. The device will adjust the reactive
power on the mains side to keep cos
Φ
within the specified acceptance range.