Table 23 (Cont.): Warnings messages.
Alarm and event messages
Corrective
action
Confirm that the connections are correct.
Reverse power
Description
The power value measured is negative (generated power), which might indicate that the transformers
have been connected inversely.
Corrective
action
Confirm that the connections are correct.
Wxxx
Description
Internal error.
Corrective
action
Contact the Technical Assistance Service.
Parallel filter in alarm
Description
This is a fault in one or more slaves.
Corrective
action
The device does not stop and adjusts its operation to the number of available slaves. On the slave
device status screen, “
” you can view the status and alarms for each
filter. If there is a communications error with any of the slaves, stop the devices and check the com-
munications wiring.
6.18.- TEMPERATURE
Note:
This screen is not visible on the
“slave”
devices.
This screen,
, displays the device’s temperature range for inductances and IGBTs.
Figure 62: Temperature.
The screen displays:
Ok
, correct temperature.
High
, high temperature.
Low
, low temperature.
Use the
and
keys to navigate through the different display screens.
Summary of Contents for AFQm
Page 2: ...2 AFQm...
Page 3: ...3 AFQm CONTENIDO CONTENTS MANUAL DE INSTRUCCIONES 4 INSTRUCTION MANUAL 117...
Page 114: ...114 AFQm Manual de Instrucciones ESPA OL 14 CERTIFICADO CE...
Page 115: ...115 Manual de Instrucciones AFQm ESPA OL...
Page 116: ...116 AFQm Manual de Instrucciones ESPA OL...
Page 227: ...227 Instruction Manual AFQm ENGLISH 14 CE CERTIFICATE...
Page 228: ...228 AFQm Instruction Manual ENGLISH...