37
Notes:
1- It is highly recomened to move the power supply wiring insertion to the right, in order
to aling the cables with its connection to the terminal block.
2- Use the M10 screw and washer provided in order to connect the electric terminals.
The maximum tightening torque is 20Nm.
3- Use a M10 metallic electric terminal aligned with the required cable cross section
according to the power of the Charge Point (Max. 150 mm2). See this requirement in the
data sheet.
4- After connecting the power supply, place the shield protection over the connection
terminals
MODEL SPECIFICATIONS
MODELS
CCS CHA T2C32
CCS CHA T2S32
CCS CHA
Minimum
recommended
cable cross
sectional area *
95 mm2
95 mm2
70 mm2
Maximum cable
cross sectional
area **
150 mm2
150 mm2
150 mm2
MODEL SPECIFICATIONS
MODELS
CCS T2S32
CCS T2C32
CCS
Minimum
recommended
cable cross
sectional area *
95 mm2
95 mm2
70 mm2
Maximum cable
cross sectional
area **
150 mm2
150 mm2
150 mm2
(*) This is the minimum recommended cable cross sectional area for the maximum AC
input current (see datasheet) using multi-core copper cables with three loaded conduc-
tors for installations in conduit in a thermally insulated wall (A2 method according to
IEC-60364-5-52).
The final cross section might be different if the installation method is another one, in any
case, it has to be calculated by the installer, taking into account the cable materials, the
conditions of installation and distances.
(**) This is the maximum cable cross sectional area accepted by the Main circuit breaker
.