MODEL SPECIFICATIONS
MODELS
CCS CHA T2C63
CCS CHA T2S32
CCS CHA
CCS T2S32
Minimum
recommended
cable cross
sectional area *
70 mm2
50 mm2
25 mm2
50 mm2
Maximum cable
cross sectional
area **
95 mm2
95 mm2
95 mm2
95 mm2
MODEL SPECIFICATIONS
MODELS
CHA T2S32
CCS
CHA
Minimum
recommended
cable cross
sectional area *
50 mm2
25 mm2
25 mm2
Maximum cable
cross sectional
area **
95 mm2
95 mm2
95 mm2
(*) This is the minimum recommended cable cross sectional area for the maximum AC
input current (see datasheet) using multi-core copper cables with three loaded conduc-
tors for installations in conduit in a thermally insulated wall (A2 method according to
IEC-60364-5-52).
The final cross section might be different if the installation method is another one, in any
case, it has to be calculated by the installer, taking into account the cable materials, the
conditions of installation and distances.
(**) This is the maximum cable cross sectional area accepted by the Main circuit breaker
.
Summary of Contents for CCS CHA T2C63