No.
Description
Setting
Unit
Display conditions
Access
level
Enumeration
Min.
Max.
Increment
426 Pump 2
0: off
1: on
0
1
1
P93 Coil 2 pump = With
1
427 Pump 2 operating-hour meter
0
999999,9
0,1
h
P93 Coil 2 pump = With
1
430 External generator run order
0: off
1: on
0
1
1
P90 External generator = heater
or cooler
1
451 Heat recovery unit operating-hour meter
0
999999,9
0,1
h
P36 Heat recovery unit = Gradual speed
heat recovery unit
1
452 Heat recovery unit speed percentage
0
100
1
%
P36 Heat recovery unit = Gradual speed
heat recovery unit
1
453
Recovery unit efficiency
0
100
1
%
P38 Temperature sensor upstream of
heat recovery unit = Without
1
454
Heat recovery unit instantaneous efficiency
0
100
1
%
P38 Temperature sensor upstream of
heat recovery unit = With
1
456 Heat recovery unit bypass opening
percentage
0
100
1
%
P36 Heat recovery unit = Plate
1
470 Maintenance faults summary
0: off
1: on
0
1
1
1
471 Danger fault summary
0: off
1: on
0
1
1
1
490 Weekly programming request
0: inactive
1: active
0
1
1
1
491 State requested by the weekly programming
0: Off
1: Frost protection
2: Night cool
3: Setpoint 2 on
5: On
0
5
1
1
492 Annual programming request
0: inactive
1: active
0
1
1
1
493 State requested by the annual programming
0: Off
1: Frost protection
2: Night cool
3: Setpoint 2 on
5: On
11: Weekly prog. 1
12: Weekly prog. 2
13: Weekly prog. 3
14: Weekly prog. 4
15: Weekly prog. 5
16: Weekly prog. 6
0
16
1
1
8 - PARAMETERS
EN-57
FLOWAY