No.
Description
Setting
Unit
Display conditions
Access
level
Enumeration
By default
234 Low supply air temperature compensation setpoint in
deadband
16,0
°C
P157 Supply air compensation in
deadband
2
235 Low supply air temperature compensation proportional
band in deadband
5,0
°C
P157 Supply air compensation in
deadband
2
236 High supply air temperature compensation setpoint in
deadband
35,0
°C
P157 Supply air compensation in
deadband
2
237 High supply air temperature compensation
proportional band in deadband
5,0
°C
P157 Supply air compensation in
deadband
2
240 Supply air temperature low limit threshold
15,0
°C
2
241 Supply air temperature upper limit threshold
35,0
°C
2
242 Return air temperature low limit threshold
15,0
°C
P154 Target temperature selection =
return air
2
243 Return air temperature upper limit threshold
35,0
°C
P154 Target temperature selection =
return air
2
244 Room temperature low limit threshold
15,0
°C
P154 Target temperature selection = room
2
245 Room temperature upper limit threshold
35,0
°C
P154 Target temperature selection = room
2
248 Frost protection threshold
4,0
°C
P28 Water coil no.1 = Cooling or Heating
or Mixed
or
P29 = cold water or hot water or mixed
3
260
Min. opening percentage for coil 1 valve when unit off
0
%
P28 Water coil no.1 = Cooling or Heating
2
261 Opening percentage for the coil 2 valve when unit
stopped
0
%
P29 Water coil no.2 = Cooling or Heating
or Mixed
2
265 Fresh air temperature limit for unit operation
-12
°C
P36 Heat recovery unit = Plate and P31
Electric preheater = without
-20
P36 Heat recovery unit = Plate and P31
Electric preheater = with
3
-25
P36 Heat recovery unit = Gradual speed
3
270 Temperature setpoint compensation activation
0: Without
1: With
0
2
270.1 Heating compensation start fresh air temp.
10,0
°C
P270 = With
2
270.2 Heating compensation end fresh air temp.
-20.0
°C
P270 = With
2
270.3 Heating compensation max. setpoint difference
3,0
°C
P270 = With
2
270.5 Cooling compensation start fresh air temp.
25,0
°C
P270 = With
2
270.6 Cooling compensation end fresh air temp.
40,0
°C
P270 = With
2
270.7 Cooling compensation max. setpoint difference
2,0
°C
P270 = With
2
271
Downgraded fresh air flow rate activation
0: Without
1: With
0
2
271.1
Downgraded mode start fresh air temperature
10,0
°C
P271 = With
2
271.2
Downgraded mode end fresh air temperature
-20.0
°C
P271 = With
2
271.3 % min. flow rate in downgraded mode
30,0
%
P271 = With
2
280 Fire safety operating mode
0: off
0
P24 = with
2
1: Intake override/exhaust stop
2: Exhaust override/intake stop
3: Intake and exhaust override
P24 = with and P104 = flow rate control
282
Intake flow rate in case of fire
P110
m
3
/h
P280 = 1 or 3
2
283
Exhaust flow rate in case of fire
P110
m
3
/h
P280 = 2 or 3
2
8 - PARAMETERS
FLOWAY
EN-54