Give this model a name and, in the description box, select the xif provided using the " ... " key.
The air handling unit controller will now appear in the list of node models, which will enable as many controllers to be created in
the database as there are controllers present on the network.
The rest of the configuration (creation of the bindings on the nvi/nvo type datapoints) is carried out normally, as it would be for any
other LON product. Our PLC does not have any nci/SCPT/UCPT type datapoints. The configuration parameters are only accessible
from the HMI terminal.