3.12 - CO
2
air quality
Before activating the air quality function (P152), you need to install a CO
2
sensor in the exhaust air flow, and connect it to the
terminal strip situated in the electrics box. Refer to the unit's manual for the installation and electrical connection.
This function calculates an IAQ (Indoor Air Quality) requirement thanks to a proportional controller (P217) so that the CO
2
concentration setpoint (P216) can be monitored.
100%
0%
Air quality
setpoint P216
Air quality proportional band
P217
IAQ requirement
Air quality
P331
If the fans are under flow rate control:
Air quality control acts primarily on the fresh air rate via the mixing damper (if present), if the fresh air rate reaches 100%,
the control system then acts on the ventilation flow rate, increasing the flow rate to a maximum value controlled by parameters
P218 and P219.
0%
Maximum flow rate
P218
Regulated flow
rate setpoint
(1 or 2)
IAQ requirement
100%
If the air intake fan is under duct pressure control (P104):
Warning: this function cannot be used if the heat recovery unit's frost level is monitored by a pressure sensor or if the extraction
fan is under duct pressure control.
In this scenario where the air intake fan is under duct pressure control, the air quality sensor must be connected to terminal strip
J26-U12.
The control function only acts on the opening value of the mixing damper to allow a greater influx of fresh air.
0%
100%
% fresh air
Mixing minimum
opening percentage
1/2
IAQ requirement
100%
152
Air quality control
216
Air quality setpoint
217
Air quality proportional band
218
Air flow max setpoint on intake for air quality
219
Air flow max setpoint on exhaust for air quality
3.13 - Fire protection
When a DAD (standalone trigger sensor) is connected to the unit, the fire detection function of the control must be activated (P24).
There are several operating modes in case of fire detection:
-
Unit shut down
-
Intake fan forced to P282 flow rate and exhaust fan shut down
-
Exhaust fan forced to P283 flow rate and intake fan shut down
-
Intake fan forced to P282 flow rate and exhaust fan to P283 flow rate
24
Fire detection
280
Fire safety operating mode
282
Intake flow rate in case of fire
283
Exhaust flow rate in case of fire
The fire fault management strategy must be chosen according to the regulations in force in the AHU's country of
installation. The AHU is not a smoke extraction device.