14 - OPTIONS ET ACCESSORIES
Options
Description
Advantages
Use
HP cond. variable-speed
single-pump
Condenser hydraulic module equipped with high-pressure
variable-speed pump, drain valve, air vent and pressure
sensors. (expansion tank not included). Built-in safety
hydraulic components available in option
Easy and fast installation (plug & play), reduced power
consumption of the water circulation pump
●
Safety hydraulic components,
evap. side
Screen filter, expansion tank and relief valve integrated in
the evaporator hydraulic module
Easy and fast installation (plug & play), operating safety
●
Safety hydraulic components,
cond. side
Screen filter, expansion tank and relief valve integrated in
the condenser hydraulic module
Easy and fast installation (plug & play), operating safety
●
M2M supervision (accessory) Monitoring solution which allows customers to track and
monitor their equipment remotely in real time
Real-time expert technical support to improve equipment
availability and reports at customer hand to monitor and
optimize operating equipment.
●
Anti-vibration mounts (kit)
Elastomer anti-vibration mounts to be placed under the unit
(material classified B2 fire class according to DIN 4102).
Isolate unit from the building, avoid transmission of
vibration and associate noise to the buiding. Must be
associate with flexible connection on water side
●
Exchangers flexibles
connection (kit)
Flexibles connections on the exchanger water side
Easy installation. Limit the transmission of vibrations to the
water network
●
Exchanger water filter (kit)
Water filter
Eliminate dust in the water network
●
Without pump option
Condenser water filter (kit)
Water filter
Eliminate dust in the water network
●
Without pump option
Set point adjustment by
4-20mA signal
Connections to allow a 4-20mA signal input
Easy energy managment, allow to adjust set point by a
4-20mA external signal
●
External temperature sensor External temperature sensor control for using weather
compensation
Allow to adjust set point using weather compensation and
define authorisation operation mode to external
temperature
●
Free Cooling dry cooler
management
Control & connections to a Free Cooling Drycooler Opera
or Vextra fitted with option FC control box
Easy system managment, Extended control capabilities to
a dryccoler used in Free Cooling mode
●
Desuperheater flexibles
connection (kit)
Flexibles connections on the desuperheaterr water side
Easy installation. Limit transmission of vibrationson the
water network
Sizes 360 to 600
14.2 - Description
14.2.1 - Fixed-speed pump
This pump is factory-fitted as standard to guarantee nominal flow
in the water loop. It is a fixed-speed pump with available system
pressure. See the pump flow/pressure curves in chapters 8 and
9.
The system's nominal flow rate must be adjusted with a manual
control valve provided by the customer (see chapters 10 and 11
on controlling the nominal water flow rate).
The maximum permitted concentration of the glycol additives
(ethylene glycol or propylene glycol) is 35%.
The maximum pump suction pressure is limited to 400 kPa (4
bar) due to the valve installed the pipe that carries the water to
the unit.
The use of any other glycol type additives must be approved by
the manufacturer.
Use of hydraulic module in an open loop is
forbidden.
14.2.2 -
Variable-speed pump
This pump is factory-fitted. It is a variable-speed pump with
available system pressure. See the pump flow/pressure curve.
The system flow rate is automatically adjusted via the frequency
converter built into the pump, based on the heat rejection load
on the drycooler.
The maximum permitted concentration of the glycol additives is
35%.
The maximum pump suction pressure is limited to 400k Pa (4
bar) due to the valve installed the pipe that carries the water to
the unit.
The use of any other glycol type additives must be approved by
the manufacturer.
Use of hydraulic module in an open loop is
forbidden.
EN-55
Dynaciat LG/LGN