4 - PHYSICAL AND ELECTRICAL DATA
LGN 360 - 600 physical data
DYNACIAT LGN
360
390
450
480
520
600
Sound levels
Standard unit
Sound power
(1)
dB(A)
75,5
76,5
77,8
76,0
77,0
78,4
Sound pressure at 10m
(2)
dB(A)
43,9
44,9
46,2
44,4
45,4
46,8
Dimensions
Length
mm
880
880
880
880
880
880
Width
mm
1583
1583
1583
1583
1583
1583
Height
mm
1574
1574
1574
1574
1574
1574
Operating weight
(3)
Standard unit
kg
630
647
665
751
774
796
Unit with evaporator with single LP pump
kg
674
691
709
797
846
868
Compressors
Hermetic scroll 48.3 rev/s
Circuit A
Qty
3
3
3
2
2
2
Circuit B
Qty
-
-
-
2
2
2
No. of power stages
Qty
3
3
3
4
4
4
Refrigerant
(3)
R-410A
Oil charge
160SZ
Circuit A
l
3,3
3,3
3,6
3,3
3,3
3,6
Circuit B
l
-
-
-
3,3
3,3
3,6
Power control
Connect'Touch Control
Minimum capacity
%
33%
33%
33%
25%
25%
25%
Water type heat exchanger
Evaporator
Direct expansion plate heat exchanger
Water volume
l
15,18
17,35
19,04
23,16
26,52
29,05
Max. water-side operating pressure without hydraulic module
kPa
1000
1000
1000
1000
1000
1000
Hydraulic module (optional)
Single pump (as required)
Pump, Victaulic screen filter, drain valves (water and air), pressure sensors
Expansion tank volume
l
25
25
25
35
35
35
Expansion vessel pressure
(4)
bar
4
4
4
4
4
4
Max. water-side operating pressure with hydraulic module
kPa
400
400
400
400
400
400
Water connections with or without hydraulic module
Victaulic
®
Connections
inches
2,5
2,5
2,5
3
3
3
External diameter
mm
73
73
73
88,9
88,9
88,9
Casing paint
Colour code RAL 7035/RAL 7024
(1) in dB ref=10
-12
W, ‘A’ weighted. Declared dual-number noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). Measured
in accordance with ISO 9614-1.
(2) In dB ref 20µPa, 'A' weighted. Declared dual-number noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). For
information, calculated from the sound power Lw(A).
(3) Values are guidelines only. Refer to the unit name plate.
(4) Upon delivery, the standard preinflation of the vessels is not necessarily at the optimum value for the installation. To enable the water volume to be varied as desired,
adapt the inflation pressure to a value close to that which corresponds to the static height of the installation. Fill the installation with water (bleeding the air) to a
pressure 10 to 20 kPa higher than that of the vessel.
EN-23
Dynaciat LG/LGN
Summary of Contents for DYNACIAT LG 080
Page 1: ...DYNACIAT LG LGN 07 2018 10188 Instruction manual...
Page 2: ...Dynaciat LG LGN EN 2...
Page 3: ...EN 3 Dynaciat LG LGN...
Page 67: ...EN 67 Dynaciat LG LGN...