4 - PHYSICAL AND ELECTRICAL DATA
DYNACIAT LG/LGN evaporator or condenser with variable or fixed speed high pressure hydraulic module and single
pump option motors
N°
(2)
Description
(3)
DYNACIAT LG/LGN
360
390
450
480
520
600
1
Nominal efficiency at full load and nominal voltage
%
87,10
87,10
87,10
87,10
87,10
87,10
Nominal efficiency at 75% rated load and nominal voltage
%
84,60
84,60
84,60
84,60
84,60
84,60
Nominal efficiency at 50% rated load and nominal voltage
%
82,50
82,50
82,50
82,50
82,50
82,50
2
Efficiency level
%
IE3
IE3
IE3
IE3
IE3
IE3
3
Year of manufacture
This information varies depending on the manufacturer and model at the time of
incorporation, Please refer to the motor name plates,
4
Manufacturer's name and trademark, commercial registration number and place of
manufacturer
5
Product's model number
6
Number of motor poles
2
2
2
2
2
2
7-1
Nominal shaft power output at full load and nominal voltage (400 V)
kW
3
3
3
3
3
3
7-2
Maximum input power (400 V)
(4)
kW
3,44
3,44
3,44
3,44
3,44
3,44
8
Rated input frequency
Hz
50
50
50
50
50
50
9-1
Nominal voltage
V
400V 3P
400V 3P
400V 3P
400V 3P
400V 3P
400V 3P
9-2
Maximum current drawn (400 V)
(5)
A
6,15
6,15
6,15
6,15
6,15
6,15
10
Rated speed
rpm
2915
2915
2915
2915
2915
2915
r/s
48,58
48,58
48,58
48,58
48,58
48,58
11
Product disassembly, recycling or disposal at end of life
Disassembly using standard tools, Disposal and recycling using an appropriate
company,
12
Operating conditions for which the motor is specifically designed
I - Altitudes above sea level
m
< 1000
(6)
II - Ambient air temperature
°C
< 40
III - Maximum operating temperature
°C
Please refer to the operating conditions given in this manual or in the specific
conditions in the manufacturer selection programs.
IV - Potentially explosive atmospheres
Non-ATEX environment
DYNACIAT LG/LGN evaporator with variable speed double high pressure hydraulic module and single pump option motors
N°
(2)
Description
(3)
DYNACIAT LG/LGN
360
390
450
480
520
600
1
Nominal efficiency at full load and nominal voltage
%
87,10
87,10
87,10
87,10
88,10
88,10
Nominal efficiency at 75% rated load and nominal voltage
%
84,60
84,60
84,60
84,60
87,50
87,50
Nominal efficiency at 50% rated load and nominal voltage
%
82,50
82,50
82,50
82,50
86,5
86,5
2
Efficiency level
%
IE3
IE3
IE3
IE3
IE3
IE3
3
Year of manufacture
This information varies depending on the manufacturer and model at the
time of incorporation. Please refer to the motor name plates.
4
Manufacturer's name and trademark, commercial registration number and place of
manufacturer
5
Product's model number
6
Number of motor poles
2
2
2
2
2
2
7-1
Nominal shaft power output at full load and nominal voltage (400 V)
kW
3
3
3
3
4
4
7-2
Maximum input power (400 V)
(4)
kW
3,44
3,44
3,44
3,44
4,54
4,54
8
Rated input frequency
Hz
50
50
50
50
50
50
9-1
Nominal voltage
V
400V 3P
400V 3P
400V 3P
400V 3P
400V 3P
400V 3P
9-2
Maximum current drawn (400 V)
(5)
A
6,15
6,15
6,15
6,15
7,84
7,84
10
Rated speed
rpm
2915
2915
2915
2915
2930
2930
r/s
48,58
48,58
48,58
48,58
48,83
48,83
11
Product disassembly, recycling or disposal at end of life
Disassembly using standard tools. Disposal and recycling using an
appropriate company.
12
Operating conditions for which the motor is specifically designed
I - Altitudes above sea level
m
< 1000
(6)
II - Ambient air temperature
°C
< 40
III - Maximum operating temperature
°C
Please refer to the operating conditions given in this manual or in the
specific conditions in the manufacturer selection programs.
IV - Potentially explosive atmospheres
Non-ATEX environment
(1) Additional electrical data required by regulation No. 640/2009 concerning the application of directive 2009/125/EC on the eco-design requirements for electric
motors.
(2) Item number imposed by regulation No. 640/2009, annex I2b.
(3) Description given by regulation No. 640/2009, annex I2b.
(4) To obtain the maximum input power for a unit with hydraulic module, add the "maximum unit input power" from the electrical data table to the pump power.
(5) To obtain the maximum unit operating current draw for a unit with hydraulic module add the "maximum unit current draw" from the electrical data table to the pump
current draw.
(6) Above 1000 m, a degradation of 3% for each 500 m should be taken into consideration.