4 - PHYSICAL AND ELECTRICAL DATA
DYNACIAT LG/LGN condenser with variable or fixed speed low pressure hydraulic module and single pump option motors
No.
(2)
Description
(3)
DYNACIAT LG
360
390
450
480
520
600
1
Nominal efficiency at full load and nominal voltage
%
85,90
85,90
85,90
85,90
85,90
85,90
Nominal efficiency at 75% rated load and nominal voltage
%
85,90
85,90
85,90
85,90
85,90
85,90
Nominal efficiency at 50% rated load and nominal voltage
%
84,50
84,50
84,50
84,50
84,50
84,50
2
Efficiency level
%
IE3
IE3
IE3
IE3
IE3
IE3
3
Year of manufacture
This information varies depending on the manufacturer and model at the time of
incorporation, Please refer to the motor name plates,
4
Manufacturer's name and trademark, commercial registration number and place of
manufacturer
5
Product's model number
6
Number of motor poles
2
2
2
2
2
2
7-1
Nominal shaft power output at full load and nominal voltage (400 V)
kW
2,2
2,2
2,2
2,2
2,2
2,2
7-2
Maximum input power (400 V)
(4)
kW
2,56
2,56
2,56
2,56
2,56
2,56
8
Rated input frequency
Hz
50
50
50
50
50
50
9-1
Nominal voltage
V
400V 3P
400V 3P
400V 3P
400V 3P
400V 3P
400V 3P
9-2
Maximum current drawn (400 V)
(5)
A
4,5
4,5
4,5
4,5
4,5
4,5
10
Rated speed
rpm
2890
2890
2890
2890
2890
2890
r/s
48,17
48,17
48,17
48,17
48,17
48,17
11
Product disassembly, recycling or disposal at end of life
Disassembly using standard tools, Disposal and recycling using an appropriate
company,
12
Operating conditions for which the motor is specifically designed
I - Altitudes above sea level
m
< 1000
(6)
II - Ambient air temperature
°C
< 40
III - Maximum operating temperature
°C
Please refer to the operating conditions given in this manual or in the specific
conditions in the manufacturer selection programs.
IV - Potentially explosive atmospheres
Non-ATEX environment
DYNACIAT LG/LGN evaporator or condenser with variable speed high pressure hydraulic module and single pump option
motors
N°
(2)
Description
(3)
DYNACIAT LG/LGN
080
090
100
120
130
150
180
200
240
260
300
1
Nominal efficiency at full load and nominal voltage
%
83,4
83,4
83,4
83,4
83,4
83,4
84,8
84,8
84,8
84,8
84,8
Nominal efficiency at 75% rated load and nominal voltage
%
81,2
81,2
81,2
81,2
81,2
81,2
82,2
82,2
82,2
82,2
82,2
Nominal efficiency at 50% rated load and nominal voltage
%
78,3
78,3
78,3
78,3
78,3
78,3
79,0
79,0
79,0
79,0
79,0
2
Efficiency level
%
IE3
IE3
IE3
IE3
IE3
IE3
IE3
IE3
IE3
IE3
IE3
3
Year of manufacture
This information varies depending on the manufacturer and model at the time of incorporation,
Please refer to the motor name plates,
4
Manufacturer's name and trademark, commercial registration number
and head office of manufacturer
5
Product's model number
6
Number of motor poles
2
2
2
2
2
2
2
2
2
2
2
7-1
Nominal shaft power output at full load and nominal voltage
(400 V)
kW
1,3
1,3
1,3
1,3
1,3
1,3
1,7
1,7
1,7
1,7
1,7
7-2
Maximum input power (400 V)
(4)
kW
1,6
1,6
1,6
1,6
1,6
1,6
2,4
2,4
2,4
2,4
2,4
8
Rated input frequency
Hz
50
50
50
50
50
50
50
50
50
50
50
9-1
Nominal voltage
V
400V
3P
400V
3P
400V
3P
400V
3P
400V
3P
400V
3P
400V
3P
400V
3P
400V
3P
400V
3P
400V
3P
9-2
Maximum current drawn (400 V)
(5)
A
2,9
2,9
2,9
2,9
2,9
2,9
4,2
4,2
4,2
4,2
4,2
10
Rated speed
rpm
2890
2890
2890
2890
2890
2890
2870
2870
2870
2870
2870
r/s
48
48
48
48
48
48
48
48
48
48
48
11
Product disassembly, recycling or disposal at end of life
Disassembly using standard tools, Disposal and recycling using an appropriate company,
12
Operating conditions for which the motor is specifically designed
I - Altitudes above sea level
m
< 1000
(6)
II - Ambient air temperature
°C
< 40
III - Maximum operating temperature
°C
Please refer to the operating conditions given in this manual or in the specific conditions in the
manufacturer selection programs.
IV - Potentially explosive atmospheres
Non-ATEX environment
(1) Additional electrical data required by regulation No. 640/2009 concerning the application of directive 2009/125/EC on the eco-design requirements for electric motors.
(2) Item number imposed by regulation No. 640/2009, annex I2b.
(3) Description given by regulation No. 640/2009, annex I2b.
(4) To obtain the maximum power input for a unit with hydraulic module, add the "maximum unit power input" from the electrical data table to the pump power.
(5) To obtain the maximum unit operating current draw for a unit with hydraulic module add the "maximum unit current draw" from the electrical data table to the pump
current draw.
(6) Above 1000 m, a degradation of 3% for each 500 m should be taken into consideration.
Dynaciat LG/LGN
EN-28
Summary of Contents for DYNACIAT LG 080
Page 1: ...DYNACIAT LG LGN 07 2018 10188 Instruction manual...
Page 2: ...Dynaciat LG LGN EN 2...
Page 3: ...EN 3 Dynaciat LG LGN...
Page 67: ...EN 67 Dynaciat LG LGN...