Options
Description
Advantages
LD
ILD
Protect2 anti-corrosion
protection
Coating applied using a conversion process
which modifies the surface of the aluminium
producing a coating that is integral to the
coil. Complete immersion in a bath to ensure
100% coverage. No heat transfer variation,
tested to withstand more than 4000 hours of
salt spray as per ASTM B117
Protect2 Improved corrosion resistance of the
MCHE coils by 2, recommended for use in
moderately corrosive environments
●
No
Anticorrosion coating on
Total Free Cooling option
coils
Same anticorrosion treatment as on MCHE
condenser coils
Improved corrosion resistance, recommended
for use in moderately corrosive environments.
●
No
Anticorrosion coating on
Partial Free Cooling
option coils
Same anticorrosion treatment as on MCHE
condenser coils
Improved corrosion resistance, recommended
for use in moderately corrosive environments.
●
No
Protect4 anti-corrosion
protection
Extremely durable and flexible epoxy
polymer coating applied on micro channel
coils by electro coating process, final UV
protective topcoat. Minimal heat transfer
variation, tested to withstand more than
6000 hours of constant neutral salt spray as
per ASTM B117, improved impact resistance
as per ASTM D2794
Protect4 Improved corrosion resistance of the
MCHE coils by 4, recommended for use in
corrosive environments
●
No
Flanged evaporator
water connection kit
Victaulic piping connections with flanged
joints
Easy installation
●
●
Compressor enclosure
Compressor with enclosure
Improved aesthetics, compressor protection
against external elements (dust, sand,
water…)
●
●
EMC class. C2, as per
EN 61800-3
Additional RFI filters on the unit power line
Reduces electromagnetic interference in
accordance with the emission level required
by category C2 to allow use in the first
environment ("residential environment")
●
●
230 V electrical plug
230 VAC power source provided with plug
socket and transformer (180 VA, 0.8 A)
Enables connection of a laptop or an
electrical device during system start-up or
maintenance
●
●
Expansion tank
6-bar expansion tank built into the hydraulic
module (requires hydraulic module option)
Easy and fast installation (plug & play), and
protection of closed water systems from
excessive pressure
●
●
Electric energy meter
Electric energy meter. Display of energy
consumption, instantaneous (U, V, I) and
cumulative (kWh) on the machine interface,
data available on the communication
buses
Enables acquisition, monitoring (remote on
CMS/BMS) of energy used.
Dec. 2022
Dec. 2022
Ultra-fast capacity
recovery
Built-in battery to allow an ultra-rapid restart
whilst maintaining the unit's reliability.
Full capacity recovery in less than one minute
after power failure. Matches requirements of
typical critical mission applications. (process,
data centres)
Dec. 2022
No
Screwed water
connection sleeves for
desuperheater
DSH connections with screw connection
sleeves
Easy to install. Allows unit connection to a
screw connector
●
●
Free cooling (total)
Free cooling hydraulic coils on the two
refrigerant circuits
Energy savings for applications which require
cooling all year round (e.g.: industrial
processes, data centres)
●
No
Free cooling (partial)
Free cooling hydraulic coils on a refrigerant
circuit
Energy savings for applications with reduced
demand for cooling in the winter (e.g. office
space with computer room, meeting rooms)
●
No
Water buffer tank
module
Built-in water buffer tank module
Avoids short cycle on compressors and
ensures stable water in the loop
●
●
Anti-vibration mounts
Elastomer anti-vibration mounts to be placed
under the unit (material classified as fire
class B2 according to DIN 4102).
Isolate the unit from the building, prevent the
transmission of vibrations and associated
noise to the building. Must be used in
conjunction with a flexible connection on the
water side
●
●
Exchangers flexible
coupling connection
Flexible connections on the exchanger water
side
Easy to install. Limits the transmission of
vibrations to the water network
●
●
Exchanger water filter
Water filter
Prevents dust entering the water network
●
●
Free cooling drycooler
management
Control and connections to an Opera or
Vextra free cooling drycooler fitted with
optional FC control box
Easy system management, extended control
capabilities to a drycooler used in free cooling
mode
●
No
Desuperheater flexible
couplings
Flexible connections on the desuperheater
water side
Easy to install. Limits the transmission of
vibrations to the water network
●
●
Water manifold
Pipe system providing a single hydraulic
connection point
Easy installation
No
2300R-4000R
Installation or application
process outside Europe
Specific management of option compatibility
Permits non-standard option compatibility for
HVAC application in the EU
●
No
12 - OPTIONS
AQUACIAT
POWER
™ LD/ILD
EN-60