AQUACIAT
POWER™
ILD
1750R
2000R
2300R
2500R
2800R
3000R
3200R
3500R
4000R
Rated short-circuit withstand currents
Rated short time (1s) current - Icw
(Module 1 / Module 2)
(a)
kA eff
20
20
20 / 20
20 / 20
20 / 20
20 / 20
20 / 20
20 / 20
20 / 20
Allowable rated peak current - Ipk
(Module 1 / Module 2)
(a)
kA pk
330
330
330 / 330 330 / 330 330 / 330 330 / 330 330 / 330 330 / 330 330 / 330
Value with upstream electrical protection
(1)
Rated conditional short circuit
current Icc (Module 1 / Module 2)
(a)
kA eff
50
50
50 / 50
50 / 50
50 / 50
50 / 50
50 / 50
50 / 50
50 / 50
Associated protection - type (Module 1/Module
2)
(a)
INS500
INS500
INS400 /
INS400
INS400 /
INS400
INS400 /
INS400
INS400 /
INS400
INS400 /
INS400
INS500 /
INS500
INS500 /
INS500
Associated protection - rating/
reference
Module 1
(a)
Micrologic
2.3 630 A /
LV432893
Micrologic
2.3 630 A /
LV432893
Micrologic
2.3 400 A /
LV432693
Micrologic
2.3 400 A /
LV432693
Micrologic
2.3 400 A /
LV432693
Micrologic
2.3 400 A /
LV432693
Micrologic
2.3 400 A /
LV432693
Micrologic
2.3 630 A /
LV432893
Micrologic
2.3 630 A /
LV432893
Module 2
(a)
-
-
Micrologic
2.3 400 A /
LV432693
Micrologic
2.3 400 A /
LV432693
Micrologic
2.3 400 A /
LV432693
Micrologic
2.3 400 A /
LV432693
Micrologic
2.3 400 A /
LV432693
Micrologic
2.3 630 A /
LV432893
Micrologic
2.3 630 A /
LV432893
(1) If another current limitation protection device is used, its time-current and thermal constraint (I²t) trip characteristics must be at least equivalent to those of the recommended
protection.
(a) Modules 1 and 2 only relate to sizes 2300R to 4000R.
Note: The short-circuit withstand current capability values above have been established for the TN system.
IT system: The short circuit holding current values given above for the TN system are not valid for IT; modifications are
required.
5.6 - Electrical data for the hydraulic module
The pumps that are factory-installed in these units have motors with efficiency class IE3 for > 0.75 kW motors. The additional electrical
data required
(1)
is as follows:
Low-pressure single pump motors for LD units (Fixed-speed single pump, hydraulic module option)
No.
(2)
Description
(3)
0602R 0650R 0750R 0900R 1100R 1200R 1350R 1400R 1600R 1750R 1800R 2000R
1
Nominal efficiency at full load and nominal
voltage
%
86,4
86,4
86,4
86,4
86,4
87,5
87,5
87,5
89,6
89,6
89,6
89,7
1
Nominal efficiency at 75% of full load and
nominal voltage
%
86,9
86,9
86,9
86,9
86,9
88,2
88,2
88,2
90,4
90,4
90,4
90
1
Nominal efficiency at 50% of full load and
nominal voltage
%
85,7
85,7
85,7
85,7
85,7
87,5
87,5
87,5
89,9
89,9
89,9
89
2
Efficiency level
-
IE3
3
Year of manufacture
-
This information varies depending on the manufacturer and model at the time of
incorporation. Please refer to the motor name plates,
4
Manufacturer's name and trademark, commercial
registration number and head office of
manufacturer
-
Same as above
5
Product model number
-
Same as above
6
Number of motor poles
-
2
7-1
Nominal shaft power output at full load and
nominal voltage (400 V)
kW
2,2
2,2
2,2
2,2
2,2
3
3
3
4
4
4
5,5
7-2
Maximum input power (400 V)
(4)
kW
2,53
2,53
2,53
2,53
2,53
3,44
3,44
3,44
4,49
4,49
4,49
6,17
8
Rated input frequency
Hz
50
9-1
Nominal voltage
V
3 x 400
9-2
Maximum current drawn (400 V)
(5)
A
4,56
4,56
4,56
4,56
4,56
6,33
6,33
6,33
7,75
7,75
7,75 10,40
10
Nominal speed
r/s
- rpm
48 - 2900
11
Product disassembly, recycling or disposal
at end of life
-
Disassembly using standard tools.
Disposal and recycling using an appropriate company
12
Operating conditions for which the motor is specifically designed
I - Altitudes above sea level
m
< 1000
(6)
II - Ambient air temperature
°C
< 40
III - Maximum operating temperature
°C
Please refer to the operating conditions given in this manual or
in the specific conditions given in the selection programs.
IV - Potentially explosive atmospheres
-
Non ATEX environment
(1) Required by regulation No. 2019/1781 concerning the application of directive 2009/125/EC on the ecodesign requirements for electric motors.
(2) Item number imposed by regulation No. 2019/1781, annex I2b.
(3) Description given by regulation No. 2019/1781, annex I2b.
(4) To obtain the maximum input power for a unit with a hydraulic module, add the "maximum operating input power" for the unit (see Electrical data table)
to the pump power.
(5) To obtain the maximum operating intensity for a unit with a hydraulic module, add the "maximum operating intensity" for the unit (see Electrical data table)
to the pump intensity.
(6) Above 1000 m, a degradation of 3% for each 500 m should be taken into consideration.
5 - PHYSICAL AND ELECTRICAL DATA FOR THE UNITS
EN-17
AQUACIAT
POWER
™ LD/ILD