![CIAT AQUACIATPOWER ILD 0602R Instruction Manual Download Page 22](http://html1.mh-extra.com/html/ciat/aquaciatpower-ild-0602r/aquaciatpower-ild-0602r_instruction-manual_2606681022.webp)
5 - PHYSICAL AND ELECTRICAL DATA FOR THE UNITS
High-pressure dual pumps for ILD units (Fixed- and variable-speed dual pumps, hydraulic module option)
No.
(2)
Description
(3)
0602R 0700R 0800R 0900R 1000R 1150R 1250R 1400R 1500R 1600R
1
Nominal efficiency at full load and nominal voltage
%
87,5
87,5
89,6
89,6
89,6
89,7
89,7
90,8
90,8
90,8
1
Nominal efficiency at 75% of full load and nominal
voltage
%
88,2
88,2
90,4
90,4
90,4
90
90
90,8
90,8
90,8
1
Nominal efficiency at 50% of full load and nominal
voltage
%
87,5
87,5
89,9
89,9
89,9
89
89
89,6
89,6
89,6
2
Efficiency level
-
IE3
3
Year of manufacture
-
This information varies depending on the manufacturer and model at the time of
incorporation. Please refer to the motor name plates,
4
Manufacturer's name and trademark, commercial
registration number and head office of manufacturer
-
Same as above
5
Product model number
-
Same as above
6
Number of motor poles
-
2
7-1
Nominal capacity on the shaft at full-load and nominal
voltage Module 1/Module 2
(a)
(400 V)
kW
3
3
4
4
4
5,5
5,5
7,5
7,5
7,5
7-2
Maximum input power, Module 1/Module 2
(a)
(400 V)
(4)
kW
3,44
3,44
4,49
4,49
4,49
6,17
6,17
8,32
8,32
8,32
8
Rated input frequency
Hz
50
9-1
Nominal voltage
V
3 x 400
9-2
Maximum input power, Module 1/Module 2
(a)
(400 V)
(5)
A
6,33
6,33
7,75
7,75
7,75
10,40 10,40 14,10 14,10 14,10
10
Nominal speed
r/s - rpm
48 - 2900
11
Product disassembly, recycling or disposal at end of life
-
Disassembly using standard tools.
Disposal and recycling using an appropriate company
12
Operating conditions for which the motor is specifically designed
I - Altitudes above sea level
m
< 1000
(6)
II - Ambient air temperature
°C
< 40
III - Maximum operating temperature
°C
Please refer to the operating conditions given in this manual or in the specific
conditions given in the selection programs.
IV - Potentially explosive atmospheres
-
Non ATEX environment
No.
(2)
Description
(3)
1750R 2000R 2300R 2500R 2800R 3000R 3200R 3500R 4000R
1
Nominal efficiency at full load and nominal voltage
%
90,8
90,8
89,7
89,7
89,7
89,7
90,8
90,8
90,8
1
Nominal efficiency at 75% of full load and nominal
voltage
%
90,8
90,8
90
90
90
90
90,8
90,8
90,8
1
Nominal efficiency at 50% of full load and nominal
voltage
%
89,6
89,6
89
89
89
89
89,6
89,6
89,6
2
Efficiency level
-
IE3
3
Year of manufacture
-
This information varies depending on the manufacturer and model at the time
of incorporation. Please refer to the motor name plates,
4
Manufacturer's name and trademark, commercial
registration number and head office of manufacturer
-
Same as above
5
Product model number
-
Same as above
6
Number of motor poles
-
2
7-1
Nominal capacity on the shaft at full-load and nominal
voltage Module 1/Module 2
(a)
(400 V)
kW
7,5
7,5
5,5 / 5,5 5,5 / 5,5 5,5 / 5,5 5,5 / 5,5 7,5 / 7,5 7,5 / 7,5 7,5 / 7,5
7-2
Maximum input power, Module 1/Module 2
(a)
(400 V)
(4)
kW
8,32
8,32
6,17 /
6,17
6,17 /
6,17
6,17 /
6,17
6,17 /
6,17
8,32 /
8,32
8,32 /
8,32
8,32 /
8,32
8
Rated input frequency
Hz
50
9-1
Nominal voltage
V
3 x 400
9-2
Maximum input power, Module 1/Module 2
(a)
(400 V)
(5)
A
14,10
14,10 14,10 /
14,10
14,10 /
14,10
14,10 /
14,10
14,10 /
14,10
14,10 /
14,10
14,10 /
14,10
14,10 /
14,10
10
Nominal speed
r/s
- rpm
48 - 2900
11
Product disassembly, recycling or disposal at end of life
-
Disassembly using standard tools. Disposal and recycling using an
appropriate company
12
Operating conditions for which the motor is specifically designed
I - Altitudes above sea level
m
< 1000
(6)
II - Ambient air temperature
°C
< 40
III - Maximum operating temperature
°C
Please refer to the operating conditions given in this manual or in the specific
conditions given in the selection programs.
IV - Potentially explosive atmospheres
-
Non ATEX environment
(1) Required by regulation No. 2019/1781 concerning the application of directive
2009/125/EC on the eco-design requirements for electric motors.
(2) Item number imposed by regulation No. 2019/1781, annex I2b.
(3) Description given by regulation No. 2019/1781, annex I2b.
(4) To obtain the maximum input power for a unit with a hydraulic module, add the
"maximum operating input power" for the unit (see Electrical data table) to the
pump power.
(5) To obtain the maximum operating intensity for a unit with a hydraulic module,
add the "maximum operating intensity" for the unit (see Electrical data table) to
the pump intensity.
(6) Above 1000 m, a degradation of 3% for each 500 m should be taken into
consideration.
(a) Modules 1 and 2 only relate to sizes 2300R to 4000R.
AQUACIAT
POWER
™ LD/ILD
EN-22