![CIAT AQUACIATPOWER ILD 0602R Instruction Manual Download Page 12](http://html1.mh-extra.com/html/ciat/aquaciatpower-ild-0602r/aquaciatpower-ild-0602r_instruction-manual_2606681012.webp)
5.2 - Physical data ILD 602R - 4000R
AQUACIAT
POWER™
ILD
0602R 0700R 0800R 0900R 1000R 1150R 1250R 1400R 1500R 1600R
Sound levels
Unit + High temperature option/Nominal high performance
Sound power
(1)
dB(A)
90,5 91,0 91,5 92,0 92,0 93,0 93,5 94,0 94,0 94,5
Sound pressure at 10 m
(2)
dB(A)
58,5 59,0 59,5 60,0 60,0 61,0 61,5 62,0 62,0 62,0
Standard unit
Sound power
(1)
dB(A)
88,0 88,5 89,0 89,5 89,5 90,5 91,0 91,5 91,5 92,0
Sound pressure at 10 m
(2)
dB(A)
55,5 56,0 56,5 57,0 57,0 58,0 58,5 59,5 59,5 60,0
Unit + Very Low Noise option
Sound power
(1)
dB(A)
85,0 86,0 86,5 87,0 87,0 88,0 88,0 89,0 89,0 89,5
Sound pressure at 10 m
(2)
dB(A)
53,0 53,5 54,0 54,5 54,5 55,5 55,5 56,5 56,5 57,0
Unit + Ultra Low Noise option
Sound power
(1)
dB(A)
83,0 84,0 84,5 85,0 85,0 86,0 86,0 86,5 87,0 87,5
Sound pressure at 10 m
(2)
dB(A)
51,0 52,0 52,5 53,0 53,0 54,0 54,0 54,5 55,0 55,5
Dimensions
Standard unit
Length
mm
2410 2410 2410 2410 2410 3604 3604 3604 3604 4798
Width
mm
2253 2253 2253 2253 2253 2253 2253 2253 2253 2253
Height
mm
2324 2324 2324 2324 2324 2324 2324 2324 2324 2324
Unit + water buffer tank module option
(3)
mm
3604 3604 3604 3604 3604 4798 4798 4798 4798 5992
Length
mm
3604 3604 3604 3604 3604 4798 4798 4798 4798 5992
Operating weight
(3)
Standard unit
kg
1569 1575 1784 1811 1817 2394 2452 2672 2678 3154
Unit + Ultra Low Noise option
kg
1672 1678 1918 1946 1952 2552 2611 2855 2861 3361
Unit + Ultra Low Noise + HP dual-pump hydraulic module option
kg
1808 1814 2065 2092 2098 2747 2806 3089 3095 3595
Unit + Ultra Low Noise + HP dual-pump hydraulic Water
buffer tank module option
kg
2791 2797 3048 3075 3081 3756 3815 4098 4104 4595
Compressors
Hermetic Scroll 48.3 r/s
Circuit A/C
1
1
2
2
2
2
2
2
2
3
Circuit B/D
2
2
2
2
2
3
3
4
4
4
Number of power stages
3
3
4
4
4
5
5
6
6
7
Unit PED category
III
III
III
III
III
III
IV
IV
IV
IV
Refrigerant
(3)
R-32 / A2L/ GWP= 675 in accordance with ARI4
Circuit A/C
kg
10,5 10,5 16,0 16,0 16,0 16,0 18,0 18,0 18,0 29,0
tCO
2
e
7,1
7,1
10,8 10,8 10,8 10,8 12,2 12,2 12,2 19,6
Circuit B/D
kg
16,0 16,0 16,0 16,0 16,0 28,5 28,5 34,0 34,0 34,5
tCO
2
e
10,8 10,8 10,8 10,8 10,8 19,2 19,2 23,0 23,0 23,3
Oil
Circuit A/C
l
6,6
6,6
13,2 13,2 13,2 13,2 13,2 13,2 13,2 22,8
Circuit B/D
l
13,2 13,2 13,2 13,2 13,2 22,8 22,8 30,4 30,4 30,4
Capacity control
Connect’Touch
Minimum capacity
%
33
33
25
25
25
20
20
17
17
14
Condenser
Grooved copper tubes and aluminium fins
Fans
Axial with rotating impeller
Standard unit
Quantity
3
3
4
4
4
5
5
6
6
7
Maximum total air flow (cooling mode)
l/s
11790 11790 15720 15720 15720 19650 19650 23580 23580 27510
Maximum rotation speed (heating mode)
r/s
12
12
12
12
12
12
12
12
12
12
Maximum total air flow (heating mode)
l/s
14460 14460 19280 19280 19280 24100 24100 28920 28920 33740
Maximum rotation speed (heating mode)
r/s
16
16
16
16
16
16
16
16
16
16
Evaporator
Dual-circuit plate heat exchanger
Water volume
l
16,2 16,2 16,2 20,7 20,7 38,7 48,6 48,6 48,6 48,6
Max. water-side operating pressure without hydraulic module
kPa
1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Hydraulic module (option)
Pump, Victaulic screen filter, relief valve, water and air vent valve,
pressure sensors
Pump
Centrifugal pump, monocell, 48.3 r/s, low- or high-pressure (as
required), single or dual (as required)
Expansion tank volume (Option)
l
50
50
50
50
50
80
80
80
80
80
Buffer tank volume (optional)
l
550
550
550
550
550
550
550
550
550
550
Max. water-side operating pressure with hydraulic module
kPa
400
400
400
400
400
400
400
400
400
400
Water connections with or without hydraulic module
Victaulic
®
type
Module 1/Module 2 connections
(a)
inches
3
3
3
3
3
4
4
4
4
4
Module 1/Module 2 external diameter
(a)
mm
88,5 88,6 88,7 88,8 88,9 114,3 114,4 114,5 114,6 114,7
Casing paint colour
Colour code RAL 7035 & 7024
(1) In dB ref=10
-12
W, (A) weighting. Declared dual-number noise emission value
in accordance with ISO 4871 with an uncertainty of +/-3 dB(A). Measured in
accordance with ISO 9614-1 and certified by Eurovent. Cooling mode operation.
(2) In dB ref 20 µPa, (A) weighting. Declared dual-number noise emission value in
accordance with ISO 4871 with an uncertainty of +/-3 dB(A). For information,
calculated from the sound power Lw(A).
(3) Values are guidelines only. Refer to the unit name plate.
(a) Modules 1 and 2 only relate to sizes 2300R to 4000R.
5 - PHYSICAL AND ELECTRICAL DATA FOR THE UNITS
AQUACIAT
POWER
™ LD/ILD
EN-12